425 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.72V (2.44%)
Voltage at Load End470.5 VLoss: 9.48 V (6976.0 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1731.32 V (360.69%)0.0 V2855.86 V (594.97%)1274458.7 WDrop/Amp High
12 AWG3.31 mm²20 A1087.96 V (226.66%)0.0 V1794.62 V (373.88%)800868.3 WDrop/Amp High
10 AWG5.26 mm²30 A684.63 V (142.63%)0.0 V1129.31 V (235.27%)503968.5 WDrop/Amp High
8 AWG8.37 mm²50 A430.24 V (89.63%)49.8 V709.7 V (147.85%)316711.4 WDrop/Amp High
6 AWG13.3 mm²65 A270.76 V (56.41%)209.2 V446.63 V (93.05%)199313.8 WDrop/Amp High
4 AWG21.15 mm²85 A170.27 V (35.47%)309.7 V280.86 V (58.51%)125336.8 WDrop/Amp High
3 AWG26.67 mm²100 A135.03 V (28.13%)345.0 V222.73 V (46.4%)99395.4 WDrop/Amp High
2 AWG33.62 mm²115 A107.11 V (22.32%)372.9 V176.69 V (36.81%)78848.1 WDrop/Amp High
1 AWG42.41 mm²130 A84.91 V (17.69%)395.1 V140.07 V (29.18%)62505.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.32 V (14.03%)412.7 V111.05 V (23.14%)49558.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.41 V (11.13%)426.6 V88.09 V (18.35%)39313.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.36 V (8.83%)437.6 V69.88 V (14.56%)31183.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.59 V (7.0%)446.4 V55.41 V (11.54%)24728.3 WDrop/Amp High
250 kcmil126.7 mm²255 A28.42 V (5.92%)451.6 V46.88 V (9.77%)20922.4 WDrop/Amp High
300 kcmil152.0 mm²285 A23.69 V (4.94%)456.3 V39.08 V (8.14%)17440.0 WDrop/Amp High
350 kcmil177.3 mm²310 A20.31 V (4.23%)459.7 V33.5 V (6.98%)14951.3 WDrop/Amp High
400 kcmil202.7 mm²335 A17.77 V (3.7%)462.2 V29.31 V (6.11%)13077.8 WDrop/Amp High
500 kcmil253.4 mm²380 A14.21 V (2.96%)465.8 V23.44 V (4.88%)10461.2 WDrop/Amp High
600 kcmil304.0 mm²420 A11.85 V (2.47%)468.2 V19.54 V (4.07%)8720.0 WDrop/Amp High
750 kcmil380.0 mm²475 A9.48 V (1.97%)470.5 V15.63 V (3.26%)6976.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A7.11 V (1.48%)472.9 V11.72 V (2.44%)5231.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 750 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 9.48V (1.97%) and delivers 470.5V at the load.

What size aluminum wire is required for 425 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.72V (2.44%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.