🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1 AWGDrop: 5.44V (2.61%)
Voltage at Load End202.8 VLoss: 5.24 V (408.6 W)
Power & Breaker (125%)16.21 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.22 V (32.32%)140.8 V110.87 V (53.31%)5239.0 WDrop/Amp High
12 AWG3.31 mm²20 A42.24 V (20.31%)165.8 V69.67 V (33.5%)3292.2 WDrop/Amp High
10 AWG5.26 mm²30 A26.58 V (12.78%)181.4 V43.84 V (21.08%)2071.7 WDrop/Amp High
8 AWG8.37 mm²50 A16.7 V (8.03%)191.3 V27.55 V (13.25%)1301.9 WDrop/Amp High
6 AWG13.3 mm²65 A10.51 V (5.05%)197.5 V17.34 V (8.34%)819.3 WDrop/Amp High
4 AWG21.15 mm²85 A6.61 V (3.18%)201.4 V10.9 V (5.24%)515.2 W~ ≤5%
3 AWG26.67 mm²100 A5.24 V (2.52%)202.8 V8.65 V (4.16%)408.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.16 V (2.0%)203.8 V6.86 V (3.3%)324.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.3 V (1.58%)204.7 V5.44 V (2.61%)256.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.61 V (1.26%)205.4 V4.31 V (2.07%)203.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.07 V (1.0%)205.9 V3.42 V (1.64%)161.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.64 V (0.79%)206.4 V2.71 V (1.3%)128.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.3 V (0.63%)206.7 V2.15 V (1.03%)101.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.1 V (0.53%)206.9 V1.82 V (0.88%)86.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.92 V (0.44%)207.1 V1.52 V (0.73%)71.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.79 V (0.38%)207.2 V1.3 V (0.63%)61.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.69 V (0.33%)207.3 V1.14 V (0.55%)53.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.55 V (0.27%)207.4 V0.91 V (0.44%)43.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.22%)207.5 V0.76 V (0.36%)35.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.18%)207.6 V0.61 V (0.29%)28.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.13%)207.7 V0.46 V (0.22%)21.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 275 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.24V (2.52%) and delivers 202.8V at the load.

What size aluminum wire is required for 45 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 5.44V (2.61%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.