45 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 3.58V (2.99%)
Voltage at Load End116.5 VLoss: 3.48 V (156.4 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 750 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A211.67 V (176.4%)0.0 V349.16 V (290.97%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A133.02 V (110.85%)0.0 V219.41 V (182.85%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A83.7 V (69.75%)36.3 V138.07 V (115.06%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A52.6 V (43.84%)67.4 V86.77 V (72.31%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A33.1 V (27.59%)86.9 V54.61 V (45.51%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A20.82 V (17.35%)99.2 V34.34 V (28.62%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A16.51 V (13.76%)103.5 V27.23 V (22.69%)742.9 WDrop/Amp High
2 AWG33.62 mm²115 A13.1 V (10.91%)106.9 V21.6 V (18.0%)589.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.38 V (8.65%)109.6 V17.12 V (14.27%)467.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.23 V (6.86%)111.8 V13.58 V (11.31%)370.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.53 V (5.44%)113.5 V10.77 V (8.98%)293.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.18 V (4.32%)114.8 V8.54 V (7.12%)233.1 W~ ≤5%
4/0 AWG107.2 mm²230 A4.11 V (3.42%)115.9 V6.77 V (5.65%)184.8 W~ ≤5%
250 kcmil126.7 mm²255 A3.48 V (2.9%)116.5 V5.73 V (4.78%)156.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.9 V (2.41%)117.1 V4.78 V (3.98%)130.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.48 V (2.07%)117.5 V4.1 V (3.41%)111.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.17 V (1.81%)117.8 V3.58 V (2.99%)97.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.74 V (1.45%)118.3 V2.87 V (2.39%)78.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.45 V (1.21%)118.6 V2.39 V (1.99%)65.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.16 V (0.97%)118.8 V1.91 V (1.59%)52.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.87 V (0.72%)119.1 V1.43 V (1.19%)39.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 750 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 750 feet one-way at 120V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 3.48V (2.9%) and delivers 116.5V at the load.

What size aluminum wire is required for 45 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 3.58V (2.99%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.