475 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.17V (8.41%)
Voltage at Load End233.9 VLoss: 6.12 V (2904.4 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2979.13 V (1241.3%)0.0 V4914.17 V (2047.57%)1415085.3 WDrop/Amp High
12 AWG3.31 mm²20 A1872.08 V (780.03%)0.0 V3088.06 V (1286.69%)889237.9 WDrop/Amp High
10 AWG5.26 mm²30 A1178.06 V (490.86%)0.0 V1943.24 V (809.69%)559577.5 WDrop/Amp High
8 AWG8.37 mm²50 A740.33 V (308.47%)0.0 V1221.2 V (508.83%)351658.0 WDrop/Amp High
6 AWG13.3 mm²65 A465.91 V (194.13%)0.0 V768.53 V (320.22%)221306.6 WDrop/Amp High
4 AWG21.15 mm²85 A292.98 V (122.08%)0.0 V483.28 V (201.37%)139166.8 WDrop/Amp High
3 AWG26.67 mm²100 A232.34 V (96.81%)7.7 V383.26 V (159.69%)110362.9 WDrop/Amp High
2 AWG33.62 mm²115 A184.31 V (76.8%)55.7 V304.03 V (126.68%)87548.4 WDrop/Amp High
1 AWG42.41 mm²130 A146.11 V (60.88%)93.9 V241.02 V (100.42%)69402.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A115.85 V (48.27%)124.2 V191.09 V (79.62%)55026.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A91.9 V (38.29%)148.1 V151.59 V (63.16%)43650.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A72.89 V (30.37%)167.1 V120.24 V (50.1%)34623.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A57.8 V (24.08%)182.2 V95.35 V (39.73%)27456.9 WDrop/Amp High
250 kcmil126.7 mm²255 A48.91 V (20.38%)191.1 V80.67 V (33.61%)23231.1 WDrop/Amp High
300 kcmil152.0 mm²285 A40.77 V (16.99%)199.2 V67.25 V (28.02%)19364.3 WDrop/Amp High
350 kcmil177.3 mm²310 A34.95 V (14.56%)205.1 V57.65 V (24.02%)16601.1 WDrop/Amp High
400 kcmil202.7 mm²335 A30.57 V (12.74%)209.4 V50.43 V (21.01%)14520.9 WDrop/Amp High
500 kcmil253.4 mm²380 A24.45 V (10.19%)215.5 V40.34 V (16.81%)11615.5 WDrop/Amp High
600 kcmil304.0 mm²420 A20.38 V (8.49%)219.6 V33.62 V (14.01%)9682.2 WDrop/Amp High
750 kcmil380.0 mm²475 A16.31 V (6.79%)223.7 V26.9 V (11.21%)7745.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.23 V (5.1%)227.8 V20.17 V (8.41%)5808.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.12V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 475 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.17V (8.41%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.