475 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.47V (3.64%)
Voltage at Load End465.9 VLoss: 14.12 V (11618.6 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2580.0 V (537.5%)0.0 V4255.79 V (886.62%)2122627.9 WDrop/Amp High
12 AWG3.31 mm²20 A1621.27 V (337.76%)0.0 V2674.34 V (557.15%)1333856.8 WDrop/Amp High
10 AWG5.26 mm²30 A1020.23 V (212.55%)0.0 V1682.9 V (350.6%)839366.2 WDrop/Amp High
8 AWG8.37 mm²50 A641.15 V (133.57%)0.0 V1057.59 V (220.33%)527487.0 WDrop/Amp High
6 AWG13.3 mm²65 A403.49 V (84.06%)76.5 V665.57 V (138.66%)331959.9 WDrop/Amp High
4 AWG21.15 mm²85 A253.73 V (52.86%)226.3 V418.54 V (87.2%)208750.2 WDrop/Amp High
3 AWG26.67 mm²100 A201.21 V (41.92%)278.8 V331.91 V (69.15%)165544.3 WDrop/Amp High
2 AWG33.62 mm²115 A159.62 V (33.25%)320.4 V263.3 V (54.85%)131322.6 WDrop/Amp High
1 AWG42.41 mm²130 A126.54 V (26.36%)353.5 V208.73 V (43.48%)104104.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A100.33 V (20.9%)379.7 V165.49 V (34.48%)82540.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A79.58 V (16.58%)400.4 V131.28 V (27.35%)65476.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A63.13 V (13.15%)416.9 V104.13 V (21.69%)51935.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A50.06 V (10.43%)429.9 V82.58 V (17.2%)41185.3 WDrop/Amp High
250 kcmil126.7 mm²255 A42.36 V (8.82%)437.6 V69.87 V (14.56%)34846.6 WDrop/Amp High
300 kcmil152.0 mm²285 A35.31 V (7.36%)444.7 V58.24 V (12.13%)29046.5 WDrop/Amp High
350 kcmil177.3 mm²310 A30.27 V (6.31%)449.7 V49.93 V (10.4%)24901.7 WDrop/Amp High
400 kcmil202.7 mm²335 A26.47 V (5.52%)453.5 V43.67 V (9.1%)21781.3 WDrop/Amp High
500 kcmil253.4 mm²380 A21.18 V (4.41%)458.8 V34.93 V (7.28%)17423.3 WDrop/Amp High
600 kcmil304.0 mm²420 A17.65 V (3.68%)462.3 V29.12 V (6.07%)14523.2 WDrop/Amp High
750 kcmil380.0 mm²475 A14.12 V (2.94%)465.9 V23.29 V (4.85%)11618.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A10.59 V (2.21%)469.4 V17.47 V (3.64%)8713.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 1000 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 14.12V (2.94%) and delivers 465.9V at the load.

What size aluminum wire is required for 475 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.47V (3.64%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.