🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.59%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.49V (0.73%)
Voltage at Load End477.2 VLoss: 2.82 V (2323.7 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A516.0 V (107.5%)0.0 V851.16 V (177.32%)424525.6 WDrop/Amp High
12 AWG3.31 mm²20 A324.25 V (67.55%)155.7 V534.87 V (111.43%)266771.4 WDrop/Amp High
10 AWG5.26 mm²30 A204.05 V (42.51%)276.0 V336.58 V (70.12%)167873.2 WDrop/Amp High
8 AWG8.37 mm²50 A128.23 V (26.71%)351.8 V211.52 V (44.07%)105497.4 WDrop/Amp High
6 AWG13.3 mm²65 A80.7 V (16.81%)399.3 V133.11 V (27.73%)66392.0 WDrop/Amp High
4 AWG21.15 mm²85 A50.75 V (10.57%)429.3 V83.71 V (17.44%)41750.0 WDrop/Amp High
3 AWG26.67 mm²100 A40.24 V (8.38%)439.8 V66.38 V (13.83%)33108.9 WDrop/Amp High
2 AWG33.62 mm²115 A31.92 V (6.65%)448.1 V52.66 V (10.97%)26264.5 WDrop/Amp High
1 AWG42.41 mm²130 A25.31 V (5.27%)454.7 V41.75 V (8.7%)20820.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.07 V (4.18%)459.9 V33.1 V (6.9%)16508.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.92 V (3.32%)464.1 V26.26 V (5.47%)13095.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.63 V (2.63%)467.4 V20.83 V (4.34%)10387.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.01 V (2.09%)470.0 V16.52 V (3.44%)8237.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.47 V (1.76%)471.5 V13.97 V (2.91%)6969.3 WDrop/Amp High
300 kcmil152.0 mm²285 A7.06 V (1.47%)472.9 V11.65 V (2.43%)5809.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.05 V (1.26%)473.9 V9.99 V (2.08%)4980.3 WDrop/Amp High
400 kcmil202.7 mm²335 A5.29 V (1.1%)474.7 V8.73 V (1.82%)4356.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.24 V (0.88%)475.8 V6.99 V (1.46%)3484.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.53 V (0.74%)476.5 V5.82 V (1.21%)2904.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.82 V (0.59%)477.2 V4.66 V (0.97%)2323.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.12 V (0.44%)477.9 V3.49 V (0.73%)1742.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 200 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.82V (0.59%) and delivers 477.2V at the load.

What size aluminum wire is required for 475 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.49V (0.73%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.