🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.54V (37.82%)
Voltage at Load End11.7 VLoss: 0.34 V (163.4 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A670.3 V (5585.86%)0.0 V1105.69 V (9214.06%)318394.2 WDrop/Amp High
12 AWG3.31 mm²20 A421.22 V (3510.15%)0.0 V694.81 V (5790.11%)200078.5 WDrop/Amp High
10 AWG5.26 mm²30 A265.06 V (2208.86%)0.0 V437.23 V (3643.58%)125904.9 WDrop/Amp High
8 AWG8.37 mm²50 A166.57 V (1388.12%)0.0 V274.77 V (2289.76%)79123.0 WDrop/Amp High
6 AWG13.3 mm²65 A104.83 V (873.58%)0.0 V172.92 V (1441.0%)49794.0 WDrop/Amp High
4 AWG21.15 mm²85 A65.92 V (549.34%)0.0 V108.74 V (906.16%)31312.5 WDrop/Amp High
3 AWG26.67 mm²100 A52.28 V (435.64%)0.0 V86.23 V (718.61%)24831.6 WDrop/Amp High
2 AWG33.62 mm²115 A41.47 V (345.59%)0.0 V68.41 V (570.06%)19698.4 WDrop/Amp High
1 AWG42.41 mm²130 A32.88 V (273.96%)0.0 V54.23 V (451.9%)15615.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.07 V (217.21%)0.0 V43.0 V (358.3%)12381.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.68 V (172.31%)0.0 V34.11 V (284.22%)9821.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.4 V (136.67%)0.0 V27.05 V (225.45%)7790.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.01 V (108.38%)0.0 V21.45 V (178.78%)6177.8 WDrop/Amp High
250 kcmil126.7 mm²255 A11.0 V (91.7%)1.0 V18.15 V (151.26%)5227.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.17 V (76.44%)2.8 V15.13 V (126.09%)4357.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.86 V (65.53%)4.1 V12.97 V (108.1%)3735.3 WDrop/Amp High
400 kcmil202.7 mm²335 A6.88 V (57.32%)5.1 V11.35 V (94.55%)3267.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.5 V (45.85%)6.5 V9.08 V (75.63%)2613.5 WDrop/Amp High
600 kcmil304.0 mm²420 A4.59 V (38.22%)7.4 V7.57 V (63.04%)2178.5 WDrop/Amp High
750 kcmil380.0 mm²475 A3.67 V (30.58%)8.3 V6.05 V (50.43%)1742.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.75 V (22.93%)9.2 V4.54 V (37.82%)1307.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 225 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.87%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.54V (37.82%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.