🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.23V (9.73%)
Voltage at Load End201.9 VLoss: 6.13 V (5841.1 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2987.37 V (1436.23%)0.0 V4927.76 V (2369.12%)2845850.2 WDrop/Amp High
12 AWG3.31 mm²20 A1877.26 V (902.53%)0.0 V3096.6 V (1488.75%)1788328.8 WDrop/Amp High
10 AWG5.26 mm²30 A1181.32 V (567.94%)0.0 V1948.62 V (936.84%)1125355.2 WDrop/Amp High
8 AWG8.37 mm²50 A742.38 V (356.91%)0.0 V1224.58 V (588.74%)707212.5 WDrop/Amp High
6 AWG13.3 mm²65 A467.2 V (224.61%)0.0 V770.66 V (370.51%)445065.3 WDrop/Amp High
4 AWG21.15 mm²85 A293.79 V (141.25%)0.0 V484.62 V (232.99%)279875.6 WDrop/Amp High
3 AWG26.67 mm²100 A232.99 V (112.01%)0.0 V384.32 V (184.77%)221948.6 WDrop/Amp High
2 AWG33.62 mm²115 A184.82 V (88.86%)23.2 V304.87 V (146.57%)176066.9 WDrop/Amp High
1 AWG42.41 mm²130 A146.52 V (70.44%)61.5 V241.68 V (116.19%)139574.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A116.17 V (55.85%)91.8 V191.62 V (92.12%)110663.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A92.15 V (44.3%)115.8 V152.01 V (73.08%)87785.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A73.09 V (35.14%)134.9 V120.57 V (57.97%)69631.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A57.96 V (27.87%)150.0 V95.61 V (45.97%)55218.0 WDrop/Amp High
250 kcmil126.7 mm²255 A49.04 V (23.58%)159.0 V80.9 V (38.89%)46719.6 WDrop/Amp High
300 kcmil152.0 mm²285 A40.88 V (19.65%)167.1 V67.43 V (32.42%)38943.2 WDrop/Amp High
350 kcmil177.3 mm²310 A35.05 V (16.85%)173.0 V57.81 V (27.79%)33386.2 WDrop/Amp High
400 kcmil202.7 mm²335 A30.65 V (14.74%)177.3 V50.57 V (24.31%)29202.6 WDrop/Amp High
500 kcmil253.4 mm²380 A24.52 V (11.79%)183.5 V40.45 V (19.45%)23359.8 WDrop/Amp High
600 kcmil304.0 mm²420 A20.44 V (9.83%)187.6 V33.72 V (16.21%)19471.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.35 V (7.86%)191.6 V26.97 V (12.97%)15577.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.26 V (5.9%)195.7 V20.23 V (9.73%)11682.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 1000 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 550 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.23V (9.73%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.