🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.27%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.23V (4.21%)
Voltage at Load End473.9 VLoss: 6.13 V (5841.1 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2987.37 V (622.37%)0.0 V4927.76 V (1026.62%)2845850.2 WDrop/Amp High
12 AWG3.31 mm²20 A1877.26 V (391.1%)0.0 V3096.6 V (645.12%)1788328.8 WDrop/Amp High
10 AWG5.26 mm²30 A1181.32 V (246.11%)0.0 V1948.62 V (405.96%)1125355.2 WDrop/Amp High
8 AWG8.37 mm²50 A742.38 V (154.66%)0.0 V1224.58 V (255.12%)707212.5 WDrop/Amp High
6 AWG13.3 mm²65 A467.2 V (97.33%)12.8 V770.66 V (160.55%)445065.3 WDrop/Amp High
4 AWG21.15 mm²85 A293.79 V (61.21%)186.2 V484.62 V (100.96%)279875.6 WDrop/Amp High
3 AWG26.67 mm²100 A232.99 V (48.54%)247.0 V384.32 V (80.07%)221948.6 WDrop/Amp High
2 AWG33.62 mm²115 A184.82 V (38.5%)295.2 V304.87 V (63.51%)176066.9 WDrop/Amp High
1 AWG42.41 mm²130 A146.52 V (30.52%)333.5 V241.68 V (50.35%)139574.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A116.17 V (24.2%)363.8 V191.62 V (39.92%)110663.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A92.15 V (19.2%)387.8 V152.01 V (31.67%)87785.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A73.09 V (15.23%)406.9 V120.57 V (25.12%)69631.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A57.96 V (12.08%)422.0 V95.61 V (19.92%)55218.0 WDrop/Amp High
250 kcmil126.7 mm²255 A49.04 V (10.22%)431.0 V80.9 V (16.85%)46719.6 WDrop/Amp High
300 kcmil152.0 mm²285 A40.88 V (8.52%)439.1 V67.43 V (14.05%)38943.2 WDrop/Amp High
350 kcmil177.3 mm²310 A35.05 V (7.3%)445.0 V57.81 V (12.04%)33386.2 WDrop/Amp High
400 kcmil202.7 mm²335 A30.65 V (6.39%)449.3 V50.57 V (10.53%)29202.6 WDrop/Amp High
500 kcmil253.4 mm²380 A24.52 V (5.11%)455.5 V40.45 V (8.43%)23359.8 WDrop/Amp High
600 kcmil304.0 mm²420 A20.44 V (4.26%)459.6 V33.72 V (7.02%)19471.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.35 V (3.41%)463.6 V26.97 V (5.62%)15577.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.26 V (2.55%)467.7 V20.23 V (4.21%)11682.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 1000 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.13V (1.27%) and delivers 473.9V at the load.

What size aluminum wire is required for 550 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.23V (4.21%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.