⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.51V (4.38%)
Voltage at Load End236.8 VLoss: 3.19 V (1752.3 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1552.28 V (646.78%)0.0 V2560.54 V (1066.89%)853755.1 WDrop/Amp High
12 AWG3.31 mm²20 A975.45 V (406.44%)0.0 V1609.04 V (670.43%)536498.6 WDrop/Amp High
10 AWG5.26 mm²30 A613.83 V (255.76%)0.0 V1012.53 V (421.89%)337606.6 WDrop/Amp High
8 AWG8.37 mm²50 A385.75 V (160.73%)0.0 V636.31 V (265.13%)212163.7 WDrop/Amp High
6 AWG13.3 mm²65 A242.76 V (101.15%)0.0 V400.45 V (166.85%)133519.6 WDrop/Amp High
4 AWG21.15 mm²85 A152.66 V (63.61%)87.3 V251.82 V (104.92%)83962.7 WDrop/Amp High
3 AWG26.67 mm²100 A121.06 V (50.44%)118.9 V199.7 V (83.21%)66584.6 WDrop/Amp High
2 AWG33.62 mm²115 A96.04 V (40.02%)144.0 V158.42 V (66.01%)52820.1 WDrop/Amp High
1 AWG42.41 mm²130 A76.13 V (31.72%)163.9 V125.58 V (52.33%)41872.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.36 V (25.15%)179.6 V99.57 V (41.49%)33198.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.88 V (19.95%)192.1 V78.98 V (32.91%)26335.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.98 V (15.83%)202.0 V62.65 V (26.1%)20889.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.12 V (12.55%)209.9 V49.68 V (20.7%)16565.4 WDrop/Amp High
250 kcmil126.7 mm²255 A25.48 V (10.62%)214.5 V42.04 V (17.51%)14015.9 WDrop/Amp High
300 kcmil152.0 mm²285 A21.24 V (8.85%)218.8 V35.04 V (14.6%)11683.0 WDrop/Amp High
350 kcmil177.3 mm²310 A18.21 V (7.59%)221.8 V30.04 V (12.52%)10015.9 WDrop/Amp High
400 kcmil202.7 mm²335 A15.93 V (6.64%)224.1 V26.27 V (10.95%)8760.8 WDrop/Amp High
500 kcmil253.4 mm²380 A12.74 V (5.31%)227.3 V21.02 V (8.76%)7007.9 WDrop/Amp High
600 kcmil304.0 mm²420 A10.62 V (4.43%)229.4 V17.52 V (7.3%)5841.5 WDrop/Amp High
750 kcmil380.0 mm²475 A8.5 V (3.54%)231.5 V14.02 V (5.84%)4673.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.37 V (2.66%)233.6 V10.51 V (4.38%)3504.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 450 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.19V (1.33%) and delivers 236.8V at the load.

What size aluminum wire is required for 550 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.51V (4.38%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.