🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.97V (2.07%)
Voltage at Load End238.5 VLoss: 1.5 V (1564.0 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A733.26 V (305.53%)0.0 V1209.54 V (503.98%)762029.3 WDrop/Amp High
12 AWG3.31 mm²20 A460.78 V (191.99%)0.0 V760.07 V (316.7%)478858.3 WDrop/Amp High
10 AWG5.26 mm²30 A289.96 V (120.82%)0.0 V478.3 V (199.29%)301334.8 WDrop/Amp High
8 AWG8.37 mm²50 A182.22 V (75.93%)57.8 V300.58 V (125.24%)189369.3 WDrop/Amp High
6 AWG13.3 mm²65 A114.68 V (47.78%)125.3 V189.16 V (78.82%)119174.5 WDrop/Amp High
4 AWG21.15 mm²85 A72.11 V (30.05%)167.9 V118.95 V (49.56%)74941.9 WDrop/Amp High
3 AWG26.67 mm²100 A57.19 V (23.83%)182.8 V94.33 V (39.31%)59430.9 WDrop/Amp High
2 AWG33.62 mm²115 A45.37 V (18.9%)194.6 V74.83 V (31.18%)47145.2 WDrop/Amp High
1 AWG42.41 mm²130 A35.96 V (14.98%)204.0 V59.32 V (24.72%)37373.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.51 V (11.88%)211.5 V47.03 V (19.6%)29632.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.62 V (9.42%)217.4 V37.31 V (15.55%)23506.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.94 V (7.48%)222.1 V29.59 V (12.33%)18645.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.23 V (5.93%)225.8 V23.47 V (9.78%)14785.6 WDrop/Amp High
250 kcmil126.7 mm²255 A12.04 V (5.02%)228.0 V19.86 V (8.27%)12510.0 WDrop/Amp High
300 kcmil152.0 mm²285 A10.03 V (4.18%)230.0 V16.55 V (6.9%)10427.8 WDrop/Amp High
350 kcmil177.3 mm²310 A8.6 V (3.58%)231.4 V14.19 V (5.91%)8939.8 WDrop/Amp High
400 kcmil202.7 mm²335 A7.52 V (3.14%)232.5 V12.41 V (5.17%)7819.5 WDrop/Amp High
500 kcmil253.4 mm²380 A6.02 V (2.51%)234.0 V9.93 V (4.14%)6255.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.02 V (2.09%)235.0 V8.28 V (3.45%)5213.9 WDrop/Amp High
750 kcmil380.0 mm²475 A4.01 V (1.67%)236.0 V6.62 V (2.76%)4171.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.01 V (1.25%)237.0 V4.97 V (2.07%)3128.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 225 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.5V (0.62%) and delivers 238.5V at the load.

What size aluminum wire is required for 600 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.97V (2.07%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.