⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.89%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.07V (2.92%)
Voltage at Load End206.2 VLoss: 1.84 V (1911.7 W)
Power & Breaker (125%)216.16 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A896.21 V (430.87%)0.0 V1478.33 V (710.73%)931369.2 WDrop/Amp High
12 AWG3.31 mm²20 A563.18 V (270.76%)0.0 V928.98 V (446.62%)585271.3 WDrop/Amp High
10 AWG5.26 mm²30 A354.39 V (170.38%)0.0 V584.59 V (281.05%)368298.1 WDrop/Amp High
8 AWG8.37 mm²50 A222.71 V (107.07%)0.0 V367.37 V (176.62%)231451.4 WDrop/Amp High
6 AWG13.3 mm²65 A140.16 V (67.38%)67.8 V231.2 V (111.15%)145657.7 WDrop/Amp High
4 AWG21.15 mm²85 A88.14 V (42.37%)119.9 V145.39 V (69.9%)91595.6 WDrop/Amp High
3 AWG26.67 mm²100 A69.9 V (33.6%)138.1 V115.3 V (55.43%)72637.7 WDrop/Amp High
2 AWG33.62 mm²115 A55.45 V (26.66%)152.6 V91.46 V (43.97%)57621.9 WDrop/Amp High
1 AWG42.41 mm²130 A43.95 V (21.13%)164.0 V72.5 V (34.86%)45679.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.85 V (16.75%)173.2 V57.49 V (27.64%)36217.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.65 V (13.29%)180.4 V45.6 V (21.92%)28729.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.93 V (10.54%)186.1 V36.17 V (17.39%)22788.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.39 V (8.36%)190.6 V28.68 V (13.79%)18071.3 WDrop/Amp High
250 kcmil126.7 mm²255 A14.71 V (7.07%)193.3 V24.27 V (11.67%)15290.0 WDrop/Amp High
300 kcmil152.0 mm²285 A12.26 V (5.9%)195.7 V20.23 V (9.73%)12745.1 WDrop/Amp High
350 kcmil177.3 mm²310 A10.51 V (5.05%)197.5 V17.34 V (8.34%)10926.4 WDrop/Amp High
400 kcmil202.7 mm²335 A9.2 V (4.42%)198.8 V15.17 V (7.29%)9557.2 WDrop/Amp High
500 kcmil253.4 mm²380 A7.36 V (3.54%)200.6 V12.13 V (5.83%)7645.0 WDrop/Amp High
600 kcmil304.0 mm²420 A6.13 V (2.95%)201.9 V10.11 V (4.86%)6372.5 WDrop/Amp High
750 kcmil380.0 mm²475 A4.91 V (2.36%)203.1 V8.09 V (3.89%)5098.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.68 V (1.77%)204.3 V6.07 V (2.92%)3823.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 275 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.84V (0.89%) and delivers 206.2V at the load.

What size aluminum wire is required for 600 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.07V (2.92%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.