🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.91V (11.49%)
Voltage at Load End203.2 VLoss: 4.83 V (5438.8 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3530.53 V (1697.37%)0.0 V5823.72 V (2799.86%)3974782.5 WDrop/Amp High
12 AWG3.31 mm²20 A2218.58 V (1066.62%)0.0 V3659.62 V (1759.43%)2497748.5 WDrop/Amp High
10 AWG5.26 mm²30 A1396.1 V (671.2%)0.0 V2302.91 V (1107.17%)1571777.1 WDrop/Amp High
8 AWG8.37 mm²50 A877.36 V (421.81%)0.0 V1447.23 V (695.78%)987759.6 WDrop/Amp High
6 AWG13.3 mm²65 A552.14 V (265.45%)0.0 V910.78 V (437.87%)621620.1 WDrop/Amp High
4 AWG21.15 mm²85 A347.21 V (166.93%)0.0 V572.73 V (275.35%)390900.6 WDrop/Amp High
3 AWG26.67 mm²100 A275.35 V (132.38%)0.0 V454.19 V (218.36%)309994.3 WDrop/Amp High
2 AWG33.62 mm²115 A218.43 V (105.01%)0.0 V360.3 V (173.22%)245911.6 WDrop/Amp High
1 AWG42.41 mm²130 A173.15 V (83.25%)34.8 V285.62 V (137.32%)194943.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A137.29 V (66.0%)70.7 V226.46 V (108.87%)154562.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A108.91 V (52.36%)99.1 V179.64 V (86.37%)122609.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A86.38 V (41.53%)121.6 V142.49 V (68.51%)97253.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A68.5 V (32.93%)139.5 V113.0 V (54.33%)77122.6 WDrop/Amp High
250 kcmil126.7 mm²255 A57.96 V (27.87%)150.0 V95.61 V (45.96%)65252.9 WDrop/Amp High
300 kcmil152.0 mm²285 A48.31 V (23.23%)159.7 V79.69 V (38.31%)54391.8 WDrop/Amp High
350 kcmil177.3 mm²310 A41.42 V (19.91%)166.6 V68.32 V (32.85%)46630.3 WDrop/Amp High
400 kcmil202.7 mm²335 A36.23 V (17.42%)171.8 V59.76 V (28.73%)40787.1 WDrop/Amp High
500 kcmil253.4 mm²380 A28.98 V (13.93%)179.0 V47.8 V (22.98%)32626.5 WDrop/Amp High
600 kcmil304.0 mm²420 A24.16 V (11.61%)183.8 V39.85 V (19.16%)27195.9 WDrop/Amp High
750 kcmil380.0 mm²475 A19.32 V (9.29%)188.7 V31.88 V (15.33%)21756.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.49 V (6.97%)193.5 V23.91 V (11.49%)16316.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 1000 feet one-way at 208V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.83V (2.32%) and delivers 203.2V at the load.

What size aluminum wire is required for 650 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.91V (11.49%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.