🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 400 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.56V (4.6%)
Voltage at Load End205.1 VLoss: 2.9 V (3263.3 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 400 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1412.21 V (678.95%)0.0 V2329.49 V (1119.95%)1589913.0 WDrop/Amp High
12 AWG3.31 mm²20 A887.43 V (426.65%)0.0 V1463.85 V (703.77%)999099.4 WDrop/Amp High
10 AWG5.26 mm²30 A558.44 V (268.48%)0.0 V921.17 V (442.87%)628710.8 WDrop/Amp High
8 AWG8.37 mm²50 A350.94 V (168.72%)0.0 V578.89 V (278.31%)395103.8 WDrop/Amp High
6 AWG13.3 mm²65 A220.86 V (106.18%)0.0 V364.31 V (175.15%)248648.0 WDrop/Amp High
4 AWG21.15 mm²85 A138.88 V (66.77%)69.1 V229.09 V (110.14%)156360.2 WDrop/Amp High
3 AWG26.67 mm²100 A110.14 V (52.95%)97.9 V181.68 V (87.34%)123997.7 WDrop/Amp High
2 AWG33.62 mm²115 A87.37 V (42.01%)120.6 V144.12 V (69.29%)98364.6 WDrop/Amp High
1 AWG42.41 mm²130 A69.26 V (33.3%)138.7 V114.25 V (54.93%)77977.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.91 V (26.4%)153.1 V90.58 V (43.55%)61825.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.56 V (20.94%)164.4 V71.86 V (34.55%)49043.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.55 V (16.61%)173.4 V57.0 V (27.4%)38901.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.4 V (13.17%)180.6 V45.2 V (21.73%)30849.1 WDrop/Amp High
250 kcmil126.7 mm²255 A23.18 V (11.15%)184.8 V38.24 V (18.39%)26101.2 WDrop/Amp High
300 kcmil152.0 mm²285 A19.32 V (9.29%)188.7 V31.88 V (15.33%)21756.7 WDrop/Amp High
350 kcmil177.3 mm²310 A16.57 V (7.97%)191.4 V27.33 V (13.14%)18652.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.49 V (6.97%)193.5 V23.9 V (11.49%)16314.8 WDrop/Amp High
500 kcmil253.4 mm²380 A11.59 V (5.57%)196.4 V19.12 V (9.19%)13050.6 WDrop/Amp High
600 kcmil304.0 mm²420 A9.66 V (4.65%)198.3 V15.94 V (7.66%)10878.4 WDrop/Amp High
750 kcmil380.0 mm²475 A7.73 V (3.72%)200.3 V12.75 V (6.13%)8702.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.8 V (2.79%)202.2 V9.56 V (4.6%)6526.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 400 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 400 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.9V (1.4%) and delivers 205.1V at the load.

What size aluminum wire is required for 650 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.56V (4.6%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.