🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.75%
Aluminum Wire (≤3% Drop)3 AWGDrop: 11.01V (2.29%)
Voltage at Load End471.6 VLoss: 8.41 V (1020.0 W)
Power & Breaker (125%)58.2 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A85.55 V (17.82%)394.5 V141.11 V (29.4%)10372.1 WDrop/Amp High
12 AWG3.31 mm²20 A53.76 V (11.2%)426.2 V88.68 V (18.47%)6517.8 WDrop/Amp High
10 AWG5.26 mm²30 A33.83 V (7.05%)446.2 V55.8 V (11.63%)4101.5 WDrop/Amp High
8 AWG8.37 mm²50 A21.26 V (4.43%)458.7 V35.07 V (7.31%)2577.5 WDrop/Amp High
6 AWG13.3 mm²65 A13.38 V (2.79%)466.6 V22.07 V (4.6%)1622.1 WDrop/Amp High
4 AWG21.15 mm²85 A8.41 V (1.75%)471.6 V13.88 V (2.89%)1020.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A6.67 V (1.39%)473.3 V11.01 V (2.29%)808.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A5.29 V (1.1%)474.7 V8.73 V (1.82%)641.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.2 V (0.87%)475.8 V6.92 V (1.44%)508.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.33 V (0.69%)476.7 V5.49 V (1.14%)403.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.64 V (0.55%)477.4 V4.35 V (0.91%)319.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.09 V (0.44%)477.9 V3.45 V (0.72%)253.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.66 V (0.35%)478.3 V2.74 V (0.57%)201.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.4 V (0.29%)478.6 V2.32 V (0.48%)170.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.17 V (0.24%)478.8 V1.93 V (0.4%)141.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.0 V (0.21%)479.0 V1.66 V (0.34%)121.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.88 V (0.18%)479.1 V1.45 V (0.3%)106.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.7 V (0.15%)479.3 V1.16 V (0.24%)85.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.12%)479.4 V0.97 V (0.2%)71.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.47 V (0.1%)479.5 V0.77 V (0.16%)56.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.07%)479.6 V0.58 V (0.12%)42.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 225 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 8.41V (1.75%) and delivers 471.6V at the load.

What size aluminum wire is required for 70 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 11.01V (2.29%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.