⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 7.13V (2.97%)
Voltage at Load End233.6 VLoss: 6.45 V (451.2 W)
Power & Breaker (125%)16.8 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A263.42 V (109.76%)0.0 V434.52 V (181.05%)18439.2 WDrop/Amp High
12 AWG3.31 mm²20 A165.53 V (68.97%)74.5 V273.05 V (113.77%)11587.2 WDrop/Amp High
10 AWG5.26 mm²30 A104.17 V (43.4%)135.8 V171.82 V (71.59%)7291.6 WDrop/Amp High
8 AWG8.37 mm²50 A65.46 V (27.28%)174.5 V107.98 V (44.99%)4582.3 WDrop/Amp High
6 AWG13.3 mm²65 A41.2 V (17.17%)198.8 V67.95 V (28.31%)2883.7 WDrop/Amp High
4 AWG21.15 mm²85 A25.91 V (10.79%)214.1 V42.73 V (17.81%)1813.4 WDrop/Amp High
3 AWG26.67 mm²100 A20.54 V (8.56%)219.5 V33.89 V (14.12%)1438.1 WDrop/Amp High
2 AWG33.62 mm²115 A16.3 V (6.79%)223.7 V26.88 V (11.2%)1140.8 WDrop/Amp High
1 AWG42.41 mm²130 A12.92 V (5.38%)227.1 V21.31 V (8.88%)904.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.24 V (4.27%)229.8 V16.9 V (7.04%)717.0 W~ ≤5%
2/0 AWG67.43 mm²175 A8.13 V (3.39%)231.9 V13.4 V (5.58%)568.8 W~ ≤5%
3/0 AWG85.01 mm²200 A6.45 V (2.69%)233.6 V10.63 V (4.43%)451.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.11 V (2.13%)234.9 V8.43 V (3.51%)357.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.32 V (1.8%)235.7 V7.13 V (2.97%)302.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.6 V (1.5%)236.4 V5.95 V (2.48%)252.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.09 V (1.29%)236.9 V5.1 V (2.12%)216.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.7 V (1.13%)237.3 V4.46 V (1.86%)189.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.16 V (0.9%)237.8 V3.57 V (1.49%)151.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.8 V (0.75%)238.2 V2.97 V (1.24%)126.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.44 V (0.6%)238.6 V2.38 V (0.99%)100.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.08 V (0.45%)238.9 V1.78 V (0.74%)75.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 600 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.45V (2.69%) and delivers 233.6V at the load.

What size aluminum wire is required for 70 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 7.13V (2.97%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.