🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 25.75V (5.36%)
Voltage at Load End472.2 VLoss: 7.8 V (9461.6 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3802.1 V (792.11%)0.0 V6271.7 V (1306.6%)4609806.9 WDrop/Amp High
12 AWG3.31 mm²20 A2389.24 V (497.76%)0.0 V3941.13 V (821.07%)2896797.1 WDrop/Amp High
10 AWG5.26 mm²30 A1503.49 V (313.23%)0.0 V2480.06 V (516.68%)1822889.4 WDrop/Amp High
8 AWG8.37 mm²50 A944.85 V (196.84%)0.0 V1558.56 V (324.7%)1145567.3 WDrop/Amp High
6 AWG13.3 mm²65 A594.61 V (123.88%)0.0 V980.84 V (204.34%)720932.2 WDrop/Amp High
4 AWG21.15 mm²85 A373.92 V (77.9%)106.1 V616.79 V (128.5%)453352.2 WDrop/Amp High
3 AWG26.67 mm²100 A296.53 V (61.78%)183.5 V489.13 V (101.9%)359520.0 WDrop/Amp High
2 AWG33.62 mm²115 A235.23 V (49.01%)244.8 V388.02 V (80.84%)285199.2 WDrop/Amp High
1 AWG42.41 mm²130 A186.47 V (38.85%)293.5 V307.6 V (64.08%)226088.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A147.85 V (30.8%)332.2 V243.88 V (50.81%)179255.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A117.28 V (24.43%)362.7 V193.46 V (40.3%)142197.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A93.03 V (19.38%)387.0 V153.45 V (31.97%)112791.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A73.77 V (15.37%)406.2 V121.69 V (25.35%)89444.0 WDrop/Amp High
250 kcmil126.7 mm²255 A62.42 V (13.0%)417.6 V102.96 V (21.45%)75678.0 WDrop/Amp High
300 kcmil152.0 mm²285 A52.03 V (10.84%)428.0 V85.82 V (17.88%)63081.6 WDrop/Amp High
350 kcmil177.3 mm²310 A44.6 V (9.29%)435.4 V73.58 V (15.33%)54080.1 WDrop/Amp High
400 kcmil202.7 mm²335 A39.02 V (8.13%)441.0 V64.36 V (13.41%)47303.4 WDrop/Amp High
500 kcmil253.4 mm²380 A31.21 V (6.5%)448.8 V51.48 V (10.73%)37839.0 WDrop/Amp High
600 kcmil304.0 mm²420 A26.01 V (5.42%)454.0 V42.91 V (8.94%)31540.8 WDrop/Amp High
750 kcmil380.0 mm²475 A20.81 V (4.34%)459.2 V34.33 V (7.15%)25232.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A15.61 V (3.25%)464.4 V25.75 V (5.36%)18923.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 1000 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 7.8V (1.62%) and delivers 472.2V at the load.

What size aluminum wire is required for 700 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 25.75V (5.36%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.