🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.15V (1.07%)
Voltage at Load End478.4 VLoss: 1.56 V (1892.3 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A760.42 V (158.42%)0.0 V1254.34 V (261.32%)921961.4 WDrop/Amp High
12 AWG3.31 mm²20 A477.85 V (99.55%)2.2 V788.23 V (164.21%)579359.4 WDrop/Amp High
10 AWG5.26 mm²30 A300.7 V (62.65%)179.3 V496.01 V (103.34%)364577.9 WDrop/Amp High
8 AWG8.37 mm²50 A188.97 V (39.37%)291.0 V311.71 V (64.94%)229113.5 WDrop/Amp High
6 AWG13.3 mm²65 A118.92 V (24.78%)361.1 V196.17 V (40.87%)144186.4 WDrop/Amp High
4 AWG21.15 mm²85 A74.78 V (15.58%)405.2 V123.36 V (25.7%)90670.4 WDrop/Amp High
3 AWG26.67 mm²100 A59.31 V (12.36%)420.7 V97.83 V (20.38%)71904.0 WDrop/Amp High
2 AWG33.62 mm²115 A47.05 V (9.8%)433.0 V77.6 V (16.17%)57039.8 WDrop/Amp High
1 AWG42.41 mm²130 A37.29 V (7.77%)442.7 V61.52 V (12.82%)45217.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.57 V (6.16%)450.4 V48.78 V (10.16%)35851.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.46 V (4.89%)456.5 V38.69 V (8.06%)28439.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.61 V (3.88%)461.4 V30.69 V (6.39%)22558.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.75 V (3.07%)465.2 V24.34 V (5.07%)17888.8 WDrop/Amp High
250 kcmil126.7 mm²255 A12.48 V (2.6%)467.5 V20.59 V (4.29%)15135.6 WDrop/Amp High
300 kcmil152.0 mm²285 A10.41 V (2.17%)469.6 V17.16 V (3.58%)12616.3 WDrop/Amp High
350 kcmil177.3 mm²310 A8.92 V (1.86%)471.1 V14.72 V (3.07%)10816.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.8 V (1.63%)472.2 V12.87 V (2.68%)9460.7 WDrop/Amp High
500 kcmil253.4 mm²380 A6.24 V (1.3%)473.8 V10.3 V (2.15%)7567.8 WDrop/Amp High
600 kcmil304.0 mm²420 A5.2 V (1.08%)474.8 V8.58 V (1.79%)6308.2 WDrop/Amp High
750 kcmil380.0 mm²475 A4.16 V (0.87%)475.8 V6.87 V (1.43%)5046.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.12 V (0.65%)476.9 V5.15 V (1.07%)3784.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 200 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.56V (0.33%) and delivers 478.4V at the load.

What size aluminum wire is required for 700 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.15V (1.07%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.