⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)38× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.96%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.3V (185.8%)
Voltage at Load End11.6 VLoss: 0.36 V (249.0 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3292.72 V (27439.33%)0.0 V5431.45 V (45262.07%)2304903.5 WDrop/Amp High
12 AWG3.31 mm²20 A2069.14 V (17242.84%)0.0 V3413.12 V (28442.63%)1448398.5 WDrop/Amp High
10 AWG5.26 mm²30 A1302.06 V (10850.53%)0.0 V2147.8 V (17898.31%)911444.7 WDrop/Amp High
8 AWG8.37 mm²50 A818.26 V (6818.85%)0.0 V1349.75 V (11247.92%)572783.7 WDrop/Amp High
6 AWG13.3 mm²65 A514.95 V (4291.26%)0.0 V849.43 V (7078.58%)360466.1 WDrop/Amp High
4 AWG21.15 mm²85 A323.82 V (2698.52%)0.0 V534.16 V (4451.3%)226676.1 WDrop/Amp High
3 AWG26.67 mm²100 A256.8 V (2140.0%)0.0 V423.6 V (3530.0%)179760.0 WDrop/Amp High
2 AWG33.62 mm²115 A203.71 V (1697.61%)0.0 V336.03 V (2800.27%)142599.6 WDrop/Amp High
1 AWG42.41 mm²130 A161.49 V (1345.76%)0.0 V266.39 V (2219.88%)113044.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A128.04 V (1067.0%)0.0 V211.21 V (1760.05%)89628.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A101.57 V (846.42%)0.0 V167.54 V (1396.19%)71098.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A80.57 V (671.38%)0.0 V132.9 V (1107.46%)56395.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.89 V (532.4%)0.0 V105.39 V (878.22%)44722.0 WDrop/Amp High
250 kcmil126.7 mm²255 A54.06 V (450.46%)0.0 V89.17 V (743.06%)37839.0 WDrop/Amp High
300 kcmil152.0 mm²285 A45.06 V (375.49%)0.0 V74.33 V (619.38%)31540.8 WDrop/Amp High
350 kcmil177.3 mm²310 A38.63 V (321.91%)0.0 V63.72 V (530.99%)27040.0 WDrop/Amp High
400 kcmil202.7 mm²335 A33.79 V (281.57%)0.0 V55.73 V (464.46%)23651.7 WDrop/Amp High
500 kcmil253.4 mm²380 A27.03 V (225.23%)0.0 V44.58 V (371.53%)18919.5 WDrop/Amp High
600 kcmil304.0 mm²420 A22.53 V (187.74%)0.0 V37.16 V (309.69%)15770.4 WDrop/Amp High
750 kcmil380.0 mm²475 A18.02 V (150.19%)0.0 V29.73 V (247.75%)12616.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.52 V (112.64%)0.0 V22.3 V (185.8%)9461.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 750 feet one-way at 12V (DC), you need 38× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.96%) and delivers 11.6V at the load.

What size aluminum wire is required for 700 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.3V (185.8%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.