⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.65V (3.68%)
Voltage at Load End474.6 VLoss: 5.35 V (7414.8 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 600 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2607.16 V (543.16%)0.0 V4300.59 V (895.96%)3612583.4 WDrop/Amp High
12 AWG3.31 mm²20 A1638.33 V (341.32%)0.0 V2702.49 V (563.02%)2270143.0 WDrop/Amp High
10 AWG5.26 mm²30 A1030.97 V (214.78%)0.0 V1700.61 V (354.29%)1428550.1 WDrop/Amp High
8 AWG8.37 mm²50 A647.9 V (134.98%)0.0 V1068.73 V (222.65%)897750.7 WDrop/Amp High
6 AWG13.3 mm²65 A407.74 V (84.94%)72.3 V672.57 V (140.12%)564975.4 WDrop/Amp High
4 AWG21.15 mm²85 A256.4 V (53.42%)223.6 V422.94 V (88.11%)355280.1 WDrop/Amp High
3 AWG26.67 mm²100 A203.33 V (42.36%)276.7 V335.4 V (69.88%)281746.3 WDrop/Amp High
2 AWG33.62 mm²115 A161.3 V (33.6%)318.7 V266.07 V (55.43%)223503.1 WDrop/Amp High
1 AWG42.41 mm²130 A127.87 V (26.64%)352.1 V210.92 V (43.94%)177179.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A101.38 V (21.12%)378.6 V167.23 V (34.84%)140478.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A80.42 V (16.75%)399.6 V132.66 V (27.64%)111436.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A63.79 V (13.29%)416.2 V105.23 V (21.92%)88391.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A50.59 V (10.54%)429.4 V83.44 V (17.38%)70094.9 WDrop/Amp High
250 kcmil126.7 mm²255 A42.8 V (8.92%)437.2 V70.6 V (14.71%)59306.8 WDrop/Amp High
300 kcmil152.0 mm²285 A35.68 V (7.43%)444.3 V58.85 V (12.26%)49435.4 WDrop/Amp High
350 kcmil177.3 mm²310 A30.59 V (6.37%)449.4 V50.45 V (10.51%)42381.1 WDrop/Amp High
400 kcmil202.7 mm²335 A26.75 V (5.57%)453.2 V44.13 V (9.19%)37070.4 WDrop/Amp High
500 kcmil253.4 mm²380 A21.4 V (4.46%)458.6 V35.3 V (7.35%)29653.4 WDrop/Amp High
600 kcmil304.0 mm²420 A17.84 V (3.72%)462.2 V29.43 V (6.13%)24717.7 WDrop/Amp High
750 kcmil380.0 mm²475 A14.27 V (2.97%)465.7 V23.54 V (4.9%)19774.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.7 V (2.23%)469.3 V17.65 V (3.68%)14829.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 600 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 600 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.35V (1.11%) and delivers 474.6V at the load.

What size aluminum wire is required for 800 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.65V (3.68%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.