⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.51%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 12.52V (2.61%)
Voltage at Load End467.9 VLoss: 12.06 V (1880.5 W)
Power & Breaker (125%)74.82 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A391.07 V (81.47%)88.9 V645.09 V (134.39%)60962.3 WDrop/Amp High
12 AWG3.31 mm²20 A245.75 V (51.2%)234.2 V405.37 V (84.45%)38308.7 WDrop/Amp High
10 AWG5.26 mm²30 A154.65 V (32.22%)325.4 V255.09 V (53.14%)24106.8 WDrop/Amp High
8 AWG8.37 mm²50 A97.18 V (20.25%)382.8 V160.31 V (33.4%)15149.5 WDrop/Amp High
6 AWG13.3 mm²65 A61.16 V (12.74%)418.8 V100.89 V (21.02%)9534.0 WDrop/Amp High
4 AWG21.15 mm²85 A38.46 V (8.01%)441.5 V63.44 V (13.22%)5995.4 WDrop/Amp High
3 AWG26.67 mm²100 A30.5 V (6.35%)449.5 V50.31 V (10.48%)4754.5 WDrop/Amp High
2 AWG33.62 mm²115 A24.19 V (5.04%)455.8 V39.91 V (8.31%)3771.6 WDrop/Amp High
1 AWG42.41 mm²130 A19.18 V (4.0%)460.8 V31.64 V (6.59%)2989.9 W~ ≤5%
1/0 AWG53.49 mm²150 A15.21 V (3.17%)464.8 V25.08 V (5.23%)2370.6 W~ ≤5%
2/0 AWG67.43 mm²175 A12.06 V (2.51%)467.9 V19.9 V (4.15%)1880.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A9.57 V (1.99%)470.4 V15.78 V (3.29%)1491.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A7.59 V (1.58%)472.4 V12.52 V (2.61%)1182.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A6.42 V (1.34%)473.6 V10.59 V (2.21%)1000.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.35 V (1.11%)474.6 V8.83 V (1.84%)834.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.59 V (0.96%)475.4 V7.57 V (1.58%)715.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.01 V (0.84%)476.0 V6.62 V (1.38%)625.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.21 V (0.67%)476.8 V5.3 V (1.1%)500.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.68 V (0.56%)477.3 V4.41 V (0.92%)417.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.14 V (0.45%)477.9 V3.53 V (0.74%)333.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.61 V (0.33%)478.4 V2.65 V (0.55%)250.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 800 feet one-way at 480V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 12.06V (2.51%) and delivers 467.9V at the load.

What size aluminum wire is required for 90 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 12.52V (2.61%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.