🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.23%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 26.48V (11.03%)
Voltage at Load End234.7 VLoss: 5.35 V (8341.7 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3910.74 V (1629.47%)0.0 V6450.89 V (2687.87%)6096234.5 WDrop/Amp High
12 AWG3.31 mm²20 A2457.5 V (1023.96%)0.0 V4053.73 V (1689.05%)3830866.4 WDrop/Amp High
10 AWG5.26 mm²30 A1546.45 V (644.35%)0.0 V2550.92 V (1062.88%)2410678.3 WDrop/Amp High
8 AWG8.37 mm²50 A971.84 V (404.93%)0.0 V1603.09 V (667.95%)1514954.3 WDrop/Amp High
6 AWG13.3 mm²65 A611.6 V (254.83%)0.0 V1008.86 V (420.36%)953396.1 WDrop/Amp High
4 AWG21.15 mm²85 A384.6 V (160.25%)0.0 V634.41 V (264.34%)599535.1 WDrop/Amp High
3 AWG26.67 mm²100 A305.0 V (127.08%)0.0 V503.11 V (209.63%)475446.9 WDrop/Amp High
2 AWG33.62 mm²115 A241.95 V (100.81%)0.0 V399.1 V (166.29%)377161.4 WDrop/Amp High
1 AWG42.41 mm²130 A191.8 V (79.92%)48.2 V316.38 V (131.83%)298990.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A152.07 V (63.36%)87.9 V250.85 V (104.52%)237056.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A120.63 V (50.26%)119.4 V198.99 V (82.91%)188049.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A95.69 V (39.87%)144.3 V157.84 V (65.77%)149160.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A75.88 V (31.62%)164.1 V125.17 V (52.15%)118285.1 WDrop/Amp High
250 kcmil126.7 mm²255 A64.2 V (26.75%)175.8 V105.9 V (44.13%)100080.3 WDrop/Amp High
300 kcmil152.0 mm²285 A53.52 V (22.3%)186.5 V88.28 V (36.78%)83422.2 WDrop/Amp High
350 kcmil177.3 mm²310 A45.88 V (19.12%)194.1 V75.68 V (31.53%)71518.1 WDrop/Amp High
400 kcmil202.7 mm²335 A40.13 V (16.72%)199.9 V66.2 V (27.58%)62556.3 WDrop/Amp High
500 kcmil253.4 mm²380 A32.1 V (13.38%)207.9 V52.95 V (22.06%)50040.1 WDrop/Amp High
600 kcmil304.0 mm²420 A26.76 V (11.15%)213.2 V44.14 V (18.39%)41711.1 WDrop/Amp High
750 kcmil380.0 mm²475 A21.41 V (8.92%)218.6 V35.31 V (14.71%)33368.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A16.05 V (6.69%)223.9 V26.48 V (11.03%)25025.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 800 feet one-way at 240V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.35V (2.23%) and delivers 234.7V at the load.

What size aluminum wire is required for 900 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 26.48V (11.03%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.