325 Amp Cable Size at 100 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 0.7V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.74V (23.9%)
Voltage at Load23.3 VLine Loss: 226.0 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A927.33 V (3863.89%)0.0 V1529.67 V (6373.61%)301383.3 WDrop High
2.5 mm²24 A18 A556.4 V (2318.33%)0.0 V917.8 V (3824.17%)180830.0 WDrop High
4 mm²32 A25 A347.75 V (1448.96%)0.0 V573.62 V (2390.1%)113018.7 WDrop High
6 mm²41 A32 A231.83 V (965.97%)0.0 V382.42 V (1593.4%)75345.8 WDrop High
10 mm²57 A44 A139.1 V (579.58%)0.0 V229.45 V (956.04%)45207.5 WDrop High
16 mm²76 A59 A86.94 V (362.24%)0.0 V143.41 V (597.53%)28254.7 WDrop High
25 mm²101 A78 A55.64 V (231.83%)0.0 V91.78 V (382.42%)18083.0 WDrop High
35 mm²125 A97 A39.74 V (165.6%)0.0 V65.56 V (273.15%)12916.4 WDrop High
50 mm²151 A118 A27.82 V (115.92%)0.0 V45.89 V (191.21%)9041.5 WDrop High
70 mm²192 A150 A19.87 V (82.8%)4.1 V32.78 V (136.58%)6458.2 WDrop High
95 mm²232 A181 A14.64 V (61.01%)9.4 V24.15 V (100.64%)4758.7 WDrop High
120 mm²269 A210 A11.59 V (48.3%)12.4 V19.12 V (79.67%)3767.3 WDrop High
150 mm²309 A241 A9.27 V (38.64%)14.7 V15.3 V (63.74%)3013.8 WDrop High
185 mm²353 A275 A7.52 V (31.33%)16.5 V12.4 V (51.68%)2443.6 WDrop High
240 mm²415 A324 A5.8 V (24.15%)18.2 V9.56 V (39.84%)1883.6 WDrop High
300 mm²477 A372 A4.64 V (19.32%)19.4 V7.65 V (31.87%)1506.9 WDrop High
400 mm²570 A445 A3.48 V (14.49%)20.5 V5.74 V (23.9%)1130.2 WDrop High

FAQ — 325 Amp Cable Size at 100 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 100 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 325A over 100m at 24V (voltage drop: 0.7V or 2.9%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.