550 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 5.1V (1.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.41V (2.03%)
Voltage at Load409.9 VLine Loss: 4855.1 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1359.08 V (327.49%)0.0 V2241.85 V (540.21%)1294700.0 WDrop High
2.5 mm²24 A18 A815.45 V (196.49%)0.0 V1345.11 V (324.12%)776820.0 WDrop High
4 mm²32 A25 A509.66 V (122.81%)0.0 V840.69 V (202.58%)485512.5 WDrop High
6 mm²41 A32 A339.77 V (81.87%)75.2 V560.46 V (135.05%)323675.0 WDrop High
10 mm²57 A44 A203.86 V (49.12%)211.1 V336.28 V (81.03%)194205.0 WDrop High
16 mm²76 A59 A127.41 V (30.7%)287.6 V210.17 V (50.64%)121378.1 WDrop High
25 mm²101 A78 A81.54 V (19.65%)333.5 V134.51 V (32.41%)77682.0 WDrop High
35 mm²125 A97 A58.25 V (14.04%)356.8 V96.08 V (23.15%)55487.1 WDrop High
50 mm²151 A118 A40.77 V (9.82%)374.2 V67.26 V (16.21%)38841.0 WDrop High
70 mm²192 A150 A29.12 V (7.02%)385.9 V48.04 V (11.58%)27743.6 WDrop High
95 mm²232 A181 A21.46 V (5.17%)393.5 V35.4 V (8.53%)20442.6 WDrop High
120 mm²269 A210 A16.99 V (4.09%)398.0 V28.02 V (6.75%)16183.7 WDrop High
150 mm²309 A241 A13.59 V (3.27%)401.4 V22.42 V (5.4%)12947.0 WDrop High
185 mm²353 A275 A11.02 V (2.66%)404.0 V18.18 V (4.38%)10497.6 WDrop High
240 mm²415 A324 A8.49 V (2.05%)406.5 V14.01 V (3.38%)8091.9 WDrop High
300 mm²477 A372 A6.8 V (1.64%)408.2 V11.21 V (2.7%)6473.5 WDrop High
400 mm²570 A445 A5.1 V (1.23%)409.9 V8.41 V (2.03%)4855.1 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 100m at 415V (voltage drop: 5.1V or 1.23%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.