⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 4.08V (0.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.73V (1.62%)
Voltage at Load410.9 VLine Loss: 3884.1 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1087.27 V (261.99%)0.0 V1793.48 V (432.16%)1035760.0 WDrop High
2.5 mm²24 A18 A652.36 V (157.2%)0.0 V1076.09 V (259.3%)621456.0 WDrop High
4 mm²32 A25 A407.72 V (98.25%)7.3 V672.56 V (162.06%)388410.0 WDrop High
6 mm²41 A32 A271.82 V (65.5%)143.2 V448.37 V (108.04%)258940.0 WDrop High
10 mm²57 A44 A163.09 V (39.3%)251.9 V269.02 V (64.82%)155364.0 WDrop High
16 mm²76 A59 A101.93 V (24.56%)313.1 V168.14 V (40.52%)97102.5 WDrop High
25 mm²101 A78 A65.24 V (15.72%)349.8 V107.61 V (25.93%)62145.6 WDrop High
35 mm²125 A97 A46.6 V (11.23%)368.4 V76.86 V (18.52%)44389.7 WDrop High
50 mm²151 A118 A32.62 V (7.86%)382.4 V53.8 V (12.96%)31072.8 WDrop High
70 mm²192 A150 A23.3 V (5.61%)391.7 V38.43 V (9.26%)22194.9 WDrop High
95 mm²232 A181 A17.17 V (4.14%)397.8 V28.32 V (6.82%)16354.1 WDrop High
120 mm²269 A210 A13.59 V (3.27%)401.4 V22.42 V (5.4%)12947.0 WDrop High
150 mm²309 A241 A10.87 V (2.62%)404.1 V17.93 V (4.32%)10357.6 WDrop High
185 mm²353 A275 A8.82 V (2.12%)406.2 V14.54 V (3.5%)8398.1 WDrop High
240 mm²415 A324 A6.8 V (1.64%)408.2 V11.21 V (2.7%)6473.5 WDrop High
300 mm²477 A372 A5.44 V (1.31%)409.6 V8.97 V (2.16%)5178.8 WDrop High
400 mm²570 A445 A4.08 V (0.98%)410.9 V6.73 V (1.62%)3884.1 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 80m at 415V (voltage drop: 4.08V or 0.98%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.