700 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 12.97V (1.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 42.8V (6.2%)
Voltage at Load677.0 VLine Loss: 15729.0 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6918.97 V (1002.75%)0.0 V11413.06 V (1654.07%)8388800.0 WDrop High
2.5 mm²24 A18 A4151.38 V (601.65%)0.0 V6847.84 V (992.44%)5033280.0 WDrop High
4 mm²32 A25 A2594.61 V (376.03%)0.0 V4279.9 V (620.28%)3145800.0 WDrop High
6 mm²41 A32 A1729.74 V (250.69%)0.0 V2853.27 V (413.52%)2097200.0 WDrop High
10 mm²57 A44 A1037.84 V (150.41%)0.0 V1711.96 V (248.11%)1258320.0 WDrop High
16 mm²76 A59 A648.65 V (94.01%)41.3 V1069.97 V (155.07%)786450.0 WDrop High
25 mm²101 A78 A415.14 V (60.16%)274.9 V684.78 V (99.24%)503328.0 WDrop High
35 mm²125 A97 A296.53 V (42.97%)393.5 V489.13 V (70.89%)359520.0 WDrop High
50 mm²151 A118 A207.57 V (30.08%)482.4 V342.39 V (49.62%)251664.0 WDrop High
70 mm²192 A150 A148.26 V (21.49%)541.7 V244.57 V (35.44%)179760.0 WDrop High
95 mm²232 A181 A109.25 V (15.83%)580.8 V180.21 V (26.12%)132454.7 WDrop High
120 mm²269 A210 A86.49 V (12.53%)603.5 V142.66 V (20.68%)104860.0 WDrop High
150 mm²309 A241 A69.19 V (10.03%)620.8 V114.13 V (16.54%)83888.0 WDrop High
185 mm²353 A275 A56.1 V (8.13%)633.9 V92.54 V (13.41%)68017.3 WDrop High
240 mm²415 A324 A43.24 V (6.27%)646.8 V71.33 V (10.34%)52430.0 WDrop High
300 mm²477 A372 A34.59 V (5.01%)655.4 V57.07 V (8.27%)41944.0 WDrop High
400 mm²570 A445 A25.95 V (3.76%)664.1 V42.8 V (6.2%)31458.0 WDrop High

FAQ — 700 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 400m at 690V (voltage drop: 12.97V or 1.88%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.