Kabeltværsnit for 110 Ampere ved 90 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 90 m ved 230V.
Copper Cable (≤3% Drop)70 mm²Drop: 6.05V (2.63%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.82V (2.53%)
Voltage at Load223.9 VLine Loss: 665.8 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 282.48 V (122.82%) | 0.0 V | 465.96 V (202.59%) | 31072.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 169.49 V (73.69%) | 60.5 V | 279.58 V (121.55%) | 18643.7 W | Drop High |
| 4 mm² | 32 A | 25 A | 105.93 V (46.06%) | 124.1 V | 174.73 V (75.97%) | 11652.3 W | Drop High |
| 6 mm² | 41 A | 32 A | 70.62 V (30.7%) | 159.4 V | 116.49 V (50.65%) | 7768.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 42.37 V (18.42%) | 187.6 V | 69.89 V (30.39%) | 4660.9 W | Drop High |
| 16 mm² | 76 A | 59 A | 26.48 V (11.51%) | 203.5 V | 43.68 V (18.99%) | 2913.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 16.95 V (7.37%) | 213.1 V | 27.96 V (12.16%) | 1864.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 12.11 V (5.26%) | 217.9 V | 19.97 V (8.68%) | 1331.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 8.47 V (3.68%) | 221.5 V | 13.98 V (6.08%) | 932.2 W | ~ ≤5% |
| 70 mm² | 192 A | 150 A | 6.05 V (2.63%) | 223.9 V | 9.98 V (4.34%) | 665.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 4.46 V (1.94%) | 225.5 V | 7.36 V (3.2%) | 490.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 3.53 V (1.54%) | 226.5 V | 5.82 V (2.53%) | 388.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.82 V (1.23%) | 227.2 V | 4.66 V (2.03%) | 310.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.29 V (1.0%) | 227.7 V | 3.78 V (1.64%) | 251.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.77 V (0.77%) | 228.2 V | 2.91 V (1.27%) | 194.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.41 V (0.61%) | 228.6 V | 2.33 V (1.01%) | 155.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.06 V (0.46%) | 228.9 V | 1.75 V (0.76%) | 116.5 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 90 Meter (230V)
Hvilket kabeltværsnit kræves til 110A ved 90 meter (230V)?
Til 110 Ampere over 90 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 6.05V / 2.63%).
Hvor mange kW svarer 110A ved 230V til?
Det svarer til 25.3 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 90m (230V)16A · 90m (230V)20A · 90m (230V)25A · 90m (230V)32A · 90m (230V)40A · 90m (230V)50A · 90m (230V)63A · 90m (230V)80A · 90m (230V)100A · 90m (230V)125A · 90m (230V)160A · 90m (230V)200A · 90m (230V)