Kabelarea för 425 Ampere vid 300 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 300 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 11.81V (2.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.49V (4.87%)
Voltage at Load388.2 VLine Loss: 8697.1 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3150.6 V (787.65%)0.0 V5197.02 V (1299.25%)2319225.0 WDrop High
2.5 mm²24 A18 A1890.36 V (472.59%)0.0 V3118.21 V (779.55%)1391535.0 WDrop High
4 mm²32 A25 A1181.48 V (295.37%)0.0 V1948.88 V (487.22%)869709.4 WDrop High
6 mm²41 A32 A787.65 V (196.91%)0.0 V1299.25 V (324.81%)579806.2 WDrop High
10 mm²57 A44 A472.59 V (118.15%)0.0 V779.55 V (194.89%)347883.8 WDrop High
16 mm²76 A59 A295.37 V (73.84%)104.6 V487.22 V (121.81%)217427.3 WDrop High
25 mm²101 A78 A189.04 V (47.26%)211.0 V311.82 V (77.96%)139153.5 WDrop High
35 mm²125 A97 A135.03 V (33.76%)265.0 V222.73 V (55.68%)99395.4 WDrop High
50 mm²151 A118 A94.52 V (23.63%)305.5 V155.91 V (38.98%)69576.7 WDrop High
70 mm²192 A150 A67.51 V (16.88%)332.5 V111.36 V (27.84%)49697.7 WDrop High
95 mm²232 A181 A49.75 V (12.44%)350.3 V82.06 V (20.51%)36619.3 WDrop High
120 mm²269 A210 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
150 mm²309 A241 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
185 mm²353 A275 A25.55 V (6.39%)374.5 V42.14 V (10.53%)18804.5 WDrop High
240 mm²415 A324 A19.69 V (4.92%)380.3 V32.48 V (8.12%)14495.2 WDrop High
300 mm²477 A372 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 W~ ≤5%
400 mm²570 A445 A11.81 V (2.95%)388.2 V19.49 V (4.87%)8697.1 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 300 Meter (400V)

Vilken kabelarea krävs för 425A vid 300 meter (400V)?

För 425 Ampere över 300 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.81V / 2.95%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.