Kabelarea för 425 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 90 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 4.73V (1.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.85V (1.46%)
Voltage at Load395.3 VLine Loss: 3478.8 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A945.18 V (236.3%)0.0 V1559.11 V (389.78%)695767.5 WDrop High
2.5 mm²24 A18 A567.11 V (141.78%)0.0 V935.46 V (233.87%)417460.5 WDrop High
4 mm²32 A25 A354.44 V (88.61%)45.6 V584.66 V (146.17%)260912.8 WDrop High
6 mm²41 A32 A236.3 V (59.07%)163.7 V389.78 V (97.44%)173941.9 WDrop High
10 mm²57 A44 A141.78 V (35.44%)258.2 V233.87 V (58.47%)104365.1 WDrop High
16 mm²76 A59 A88.61 V (22.15%)311.4 V146.17 V (36.54%)65228.2 WDrop High
25 mm²101 A78 A56.71 V (14.18%)343.3 V93.55 V (23.39%)41746.0 WDrop High
35 mm²125 A97 A40.51 V (10.13%)359.5 V66.82 V (16.7%)29818.6 WDrop High
50 mm²151 A118 A28.36 V (7.09%)371.6 V46.77 V (11.69%)20873.0 WDrop High
70 mm²192 A150 A20.25 V (5.06%)379.7 V33.41 V (8.35%)14909.3 WDrop High
95 mm²232 A181 A14.92 V (3.73%)385.1 V24.62 V (6.15%)10985.8 WDrop High
120 mm²269 A210 A11.81 V (2.95%)388.2 V19.49 V (4.87%)8697.1 WDrop High
150 mm²309 A241 A9.45 V (2.36%)390.5 V15.59 V (3.9%)6957.7 WDrop High
185 mm²353 A275 A7.66 V (1.92%)392.3 V12.64 V (3.16%)5641.4 WDrop High
240 mm²415 A324 A5.91 V (1.48%)394.1 V9.74 V (2.44%)4348.5 WDrop High
300 mm²477 A372 A4.73 V (1.18%)395.3 V7.8 V (1.95%)3478.8 W✓ OK (≤3%)
400 mm²570 A445 A3.54 V (0.89%)396.5 V5.85 V (1.46%)2609.1 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 425A vid 90 meter (400V)?

För 425 Ampere över 90 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (4.73V / 1.18%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.