⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 29.42V (6.13%)
Voltage at Load End471.1 VLoss: 8.92 V (15447.5 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4345.26 V (905.26%)0.0 V7167.65 V (1493.26%)7526215.4 WDrop/Amp High
12 AWG3.31 mm²20 A2730.56 V (568.87%)0.0 V4504.14 V (938.36%)4729464.7 WDrop/Amp High
10 AWG5.26 mm²30 A1718.28 V (357.97%)0.0 V2834.36 V (590.49%)2976146.0 WDrop/Amp High
8 AWG8.37 mm²50 A1079.83 V (224.96%)0.0 V1781.21 V (371.09%)1870314.0 WDrop/Amp High
6 AWG13.3 mm²65 A679.56 V (141.57%)0.0 V1120.96 V (233.53%)1177032.2 WDrop/Amp High
4 AWG21.15 mm²85 A427.34 V (89.03%)52.7 V704.9 V (146.85%)740166.8 WDrop/Amp High
3 AWG26.67 mm²100 A338.89 V (70.6%)141.1 V559.01 V (116.46%)586971.4 WDrop/Amp High
2 AWG33.62 mm²115 A268.83 V (56.01%)211.2 V443.45 V (92.38%)465631.4 WDrop/Amp High
1 AWG42.41 mm²130 A213.11 V (44.4%)266.9 V351.54 V (73.24%)369123.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A168.97 V (35.2%)311.0 V278.72 V (58.07%)292662.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A134.04 V (27.92%)346.0 V221.1 V (46.06%)232159.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A106.32 V (22.15%)373.7 V175.38 V (36.54%)184149.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A84.31 V (17.56%)395.7 V139.07 V (28.97%)146031.0 WDrop/Amp High
250 kcmil126.7 mm²255 A71.34 V (14.86%)408.7 V117.67 V (24.51%)123555.9 WDrop/Amp High
300 kcmil152.0 mm²285 A59.46 V (12.39%)420.5 V98.08 V (20.43%)102990.3 WDrop/Amp High
350 kcmil177.3 mm²310 A50.98 V (10.62%)429.0 V84.09 V (17.52%)88294.0 WDrop/Amp High
400 kcmil202.7 mm²335 A44.59 V (9.29%)435.4 V73.55 V (15.32%)77230.0 WDrop/Amp High
500 kcmil253.4 mm²380 A35.67 V (7.43%)444.3 V58.83 V (12.26%)61777.9 WDrop/Amp High
600 kcmil304.0 mm²420 A29.73 V (6.19%)450.3 V49.04 V (10.22%)51495.2 WDrop/Amp High
750 kcmil380.0 mm²475 A23.78 V (4.96%)456.2 V39.23 V (8.17%)41196.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A17.84 V (3.72%)462.2 V29.42 V (6.13%)30895.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 800 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 8.92V (1.86%) and delivers 471.1V at the load.

What size aluminum wire is required for 1000 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 29.42V (6.13%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.