🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.8V (23.36%)
Voltage at Load End11.7 VLoss: 0.34 V (37.4 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A413.94 V (3449.52%)0.0 V682.81 V (5690.09%)45533.6 WDrop/Amp High
12 AWG3.31 mm²20 A260.12 V (2167.67%)0.0 V429.08 V (3575.64%)28613.3 WDrop/Amp High
10 AWG5.26 mm²30 A163.69 V (1364.07%)0.0 V270.01 V (2250.07%)18005.7 WDrop/Amp High
8 AWG8.37 mm²50 A102.87 V (857.23%)0.0 V169.68 V (1414.02%)11315.4 WDrop/Amp High
6 AWG13.3 mm²65 A64.74 V (539.47%)0.0 V106.79 V (889.88%)7121.0 WDrop/Amp High
4 AWG21.15 mm²85 A40.71 V (339.24%)0.0 V67.15 V (559.59%)4478.0 WDrop/Amp High
3 AWG26.67 mm²100 A32.28 V (269.03%)0.0 V53.25 V (443.77%)3551.2 WDrop/Amp High
2 AWG33.62 mm²115 A25.61 V (213.41%)0.0 V42.24 V (352.03%)2817.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.3 V (169.18%)0.0 V33.49 V (279.07%)2233.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.1 V (134.14%)0.0 V26.55 V (221.26%)1770.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.77 V (106.41%)0.0 V21.06 V (175.52%)1404.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.13 V (84.4%)1.9 V16.71 V (139.22%)1114.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.03 V (66.93%)4.0 V13.25 V (110.4%)883.5 WDrop/Amp High
250 kcmil126.7 mm²255 A6.8 V (56.63%)5.2 V11.21 V (93.41%)747.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.66 V (47.2%)6.3 V9.34 V (77.86%)623.1 WDrop/Amp High
350 kcmil177.3 mm²310 A4.86 V (40.47%)7.1 V8.01 V (66.75%)534.2 WDrop/Amp High
400 kcmil202.7 mm²335 A4.25 V (35.4%)7.8 V7.01 V (58.39%)467.2 WDrop/Amp High
500 kcmil253.4 mm²380 A3.4 V (28.31%)8.6 V5.6 V (46.71%)373.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.83 V (23.6%)9.2 V4.67 V (38.93%)311.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.27 V (18.88%)9.7 V3.74 V (31.15%)249.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.7 V (14.16%)10.3 V2.8 V (23.36%)186.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 600 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.83%) and delivers 11.7V at the load.

What size aluminum wire is required for 110 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.8V (23.36%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.