⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.07V (2.92%)
Voltage at Load End202.1 VLoss: 5.89 V (1121.3 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A358.48 V (172.35%)0.0 V591.33 V (284.29%)68300.4 WDrop/Amp High
12 AWG3.31 mm²20 A225.27 V (108.3%)0.0 V371.59 V (178.65%)42919.9 WDrop/Amp High
10 AWG5.26 mm²30 A141.76 V (68.15%)66.2 V233.83 V (112.42%)27008.5 WDrop/Amp High
8 AWG8.37 mm²50 A89.09 V (42.83%)118.9 V146.95 V (70.65%)16973.1 WDrop/Amp High
6 AWG13.3 mm²65 A56.06 V (26.95%)151.9 V92.48 V (44.46%)10681.6 WDrop/Amp High
4 AWG21.15 mm²85 A35.26 V (16.95%)172.7 V58.15 V (27.96%)6717.0 WDrop/Amp High
3 AWG26.67 mm²100 A27.96 V (13.44%)180.0 V46.12 V (22.17%)5326.8 WDrop/Amp High
2 AWG33.62 mm²115 A22.18 V (10.66%)185.8 V36.58 V (17.59%)4225.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.58 V (8.45%)190.4 V29.0 V (13.94%)3349.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.94 V (6.7%)194.1 V22.99 V (11.05%)2655.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.06 V (5.32%)196.9 V18.24 V (8.77%)2106.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.77 V (4.22%)199.2 V14.47 V (6.96%)1671.2 W~ ≤5%
4/0 AWG107.2 mm²230 A6.96 V (3.34%)201.0 V11.47 V (5.52%)1325.2 W~ ≤5%
250 kcmil126.7 mm²255 A5.89 V (2.83%)202.1 V9.71 V (4.67%)1121.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.91 V (2.36%)203.1 V8.09 V (3.89%)934.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.21 V (2.02%)203.8 V6.94 V (3.34%)801.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.68 V (1.77%)204.3 V6.07 V (2.92%)700.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.94 V (1.41%)205.1 V4.85 V (2.33%)560.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.45 V (1.18%)205.5 V4.05 V (1.95%)467.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.96 V (0.94%)206.0 V3.24 V (1.56%)373.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.47 V (0.71%)206.5 V2.43 V (1.17%)280.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 600 feet one-way at 208V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.89V (2.83%) and delivers 202.1V at the load.

What size aluminum wire is required for 110 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.07V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.