⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.07V (2.92%)
Voltage at Load End201.9 VLoss: 6.13 V (1168.3 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A448.11 V (215.44%)0.0 V739.16 V (355.37%)85375.5 WDrop/Amp High
12 AWG3.31 mm²20 A281.59 V (135.38%)0.0 V464.49 V (223.31%)53649.9 WDrop/Amp High
10 AWG5.26 mm²30 A177.2 V (85.19%)30.8 V292.29 V (140.53%)33760.7 WDrop/Amp High
8 AWG8.37 mm²50 A111.36 V (53.54%)96.6 V183.69 V (88.31%)21216.4 WDrop/Amp High
6 AWG13.3 mm²65 A70.08 V (33.69%)137.9 V115.6 V (55.58%)13352.0 WDrop/Amp High
4 AWG21.15 mm²85 A44.07 V (21.19%)163.9 V72.69 V (34.95%)8396.3 WDrop/Amp High
3 AWG26.67 mm²100 A34.95 V (16.8%)173.1 V57.65 V (27.72%)6658.5 WDrop/Amp High
2 AWG33.62 mm²115 A27.72 V (13.33%)180.3 V45.73 V (21.99%)5282.0 WDrop/Amp High
1 AWG42.41 mm²130 A21.98 V (10.57%)186.0 V36.25 V (17.43%)4187.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.42 V (8.38%)190.6 V28.74 V (13.82%)3319.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.82 V (6.65%)194.2 V22.8 V (10.96%)2633.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.96 V (5.27%)197.0 V18.09 V (8.7%)2088.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.69 V (4.18%)199.3 V14.34 V (6.9%)1656.5 W~ ≤5%
250 kcmil126.7 mm²255 A7.36 V (3.54%)200.6 V12.13 V (5.83%)1401.6 W~ ≤5%
300 kcmil152.0 mm²285 A6.13 V (2.95%)201.9 V10.11 V (4.86%)1168.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.26 V (2.53%)202.7 V8.67 V (4.17%)1001.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.6 V (2.21%)203.4 V7.58 V (3.65%)876.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.68 V (1.77%)204.3 V6.07 V (2.92%)700.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.07 V (1.47%)204.9 V5.06 V (2.43%)584.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.45 V (1.18%)205.5 V4.05 V (1.95%)467.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.84 V (0.88%)206.2 V3.03 V (1.46%)350.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 750 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 110 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.07V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.