🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 5.9V (2.84%)
Voltage at Load End202.9 VLoss: 5.07 V (1537.3 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A261.39 V (125.67%)0.0 V431.18 V (207.3%)79231.1 WDrop/Amp High
12 AWG3.31 mm²20 A164.26 V (78.97%)43.7 V270.95 V (130.27%)49788.7 WDrop/Amp High
10 AWG5.26 mm²30 A103.37 V (49.69%)104.6 V170.5 V (81.97%)31330.9 WDrop/Amp High
8 AWG8.37 mm²50 A64.96 V (31.23%)143.0 V107.15 V (51.51%)19689.4 WDrop/Amp High
6 AWG13.3 mm²65 A40.88 V (19.65%)167.1 V67.43 V (32.42%)12391.0 WDrop/Amp High
4 AWG21.15 mm²85 A25.71 V (12.36%)182.3 V42.4 V (20.39%)7792.0 WDrop/Amp High
3 AWG26.67 mm²100 A20.39 V (9.8%)187.6 V33.63 V (16.17%)6179.3 WDrop/Amp High
2 AWG33.62 mm²115 A16.17 V (7.77%)191.8 V26.68 V (12.83%)4901.9 WDrop/Amp High
1 AWG42.41 mm²130 A12.82 V (6.16%)195.2 V21.15 V (10.17%)3885.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.16 V (4.89%)197.8 V16.77 V (8.06%)3081.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.06 V (3.88%)199.9 V13.3 V (6.39%)2444.0 W~ ≤5%
3/0 AWG85.01 mm²200 A6.4 V (3.07%)201.6 V10.55 V (5.07%)1938.6 W~ ≤5%
4/0 AWG107.2 mm²230 A5.07 V (2.44%)202.9 V8.37 V (4.02%)1537.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.29 V (2.06%)203.7 V7.08 V (3.4%)1300.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.58 V (1.72%)204.4 V5.9 V (2.84%)1084.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.07 V (1.47%)204.9 V5.06 V (2.43%)929.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.68 V (1.29%)205.3 V4.42 V (2.13%)813.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.15 V (1.03%)205.9 V3.54 V (1.7%)650.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.79 V (0.86%)206.2 V2.95 V (1.42%)542.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.43 V (0.69%)206.6 V2.36 V (1.13%)433.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.07 V (0.52%)206.9 V1.77 V (0.85%)325.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 275 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.07V (2.44%) and delivers 202.9V at the load.

What size aluminum wire is required for 175 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 5.9V (2.84%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.