⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.81V (2.84%)
Voltage at Load End234.1 VLoss: 5.86 V (1024.9 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.83 V (125.76%)0.0 V497.88 V (207.45%)52820.7 WDrop/Amp High
12 AWG3.31 mm²20 A189.67 V (79.03%)50.3 V312.87 V (130.36%)33192.5 WDrop/Amp High
10 AWG5.26 mm²30 A119.36 V (49.73%)120.6 V196.88 V (82.03%)20887.3 WDrop/Amp High
8 AWG8.37 mm²50 A75.01 V (31.25%)165.0 V123.73 V (51.55%)13126.3 WDrop/Amp High
6 AWG13.3 mm²65 A47.2 V (19.67%)192.8 V77.86 V (32.44%)8260.7 WDrop/Amp High
4 AWG21.15 mm²85 A29.68 V (12.37%)210.3 V48.96 V (20.4%)5194.7 WDrop/Amp High
3 AWG26.67 mm²100 A23.54 V (9.81%)216.5 V38.83 V (16.18%)4119.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.67 V (7.78%)221.3 V30.8 V (12.83%)3267.9 WDrop/Amp High
1 AWG42.41 mm²130 A14.8 V (6.17%)225.2 V24.42 V (10.17%)2590.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.74 V (4.89%)228.3 V19.36 V (8.07%)2054.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.31 V (3.88%)230.7 V15.36 V (6.4%)1629.3 W~ ≤5%
3/0 AWG85.01 mm²200 A7.39 V (3.08%)232.6 V12.18 V (5.08%)1292.4 W~ ≤5%
4/0 AWG107.2 mm²230 A5.86 V (2.44%)234.1 V9.66 V (4.03%)1024.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.96 V (2.06%)235.0 V8.17 V (3.41%)867.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.13 V (1.72%)235.9 V6.81 V (2.84%)722.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.54 V (1.48%)236.5 V5.84 V (2.43%)619.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.1 V (1.29%)236.9 V5.11 V (2.13%)542.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.48 V (1.03%)237.5 V4.09 V (1.7%)433.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.07 V (0.86%)237.9 V3.41 V (1.42%)361.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.65 V (0.69%)238.3 V2.73 V (1.14%)289.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.24 V (0.52%)238.8 V2.04 V (0.85%)216.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 275 feet one-way at 240V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.86V (2.44%) and delivers 234.1V at the load.

What size aluminum wire is required for 175 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.81V (2.84%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.