🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.21V (2.98%)
Voltage at Load End202.7 VLoss: 5.34 V (2079.2 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.97 V (132.2%)0.0 V453.58 V (218.07%)107160.4 WDrop/Amp High
12 AWG3.31 mm²20 A172.79 V (83.07%)35.2 V285.03 V (137.03%)67339.4 WDrop/Amp High
10 AWG5.26 mm²30 A108.73 V (52.28%)99.3 V179.36 V (86.23%)42375.2 WDrop/Amp High
8 AWG8.37 mm²50 A68.33 V (32.85%)139.7 V112.72 V (54.19%)26630.1 WDrop/Amp High
6 AWG13.3 mm²65 A43.0 V (20.67%)165.0 V70.94 V (34.1%)16758.9 WDrop/Amp High
4 AWG21.15 mm²85 A27.04 V (13.0%)181.0 V44.61 V (21.45%)10538.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.45 V (10.31%)186.6 V35.37 V (17.01%)8357.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.01 V (8.18%)191.0 V28.06 V (13.49%)6629.8 WDrop/Amp High
1 AWG42.41 mm²130 A13.49 V (6.48%)194.5 V22.25 V (10.7%)5255.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.69 V (5.14%)197.3 V17.64 V (8.48%)4167.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.48 V (4.08%)199.5 V13.99 V (6.73%)3305.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.73 V (3.23%)201.3 V11.1 V (5.34%)2622.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.34 V (2.57%)202.7 V8.8 V (4.23%)2079.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.51 V (2.17%)203.5 V7.45 V (3.58%)1759.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.76 V (1.81%)204.2 V6.21 V (2.98%)1466.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.23 V (1.55%)204.8 V5.32 V (2.56%)1257.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.82 V (1.36%)205.2 V4.65 V (2.24%)1099.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.26 V (1.09%)205.7 V3.72 V (1.79%)879.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (0.9%)206.1 V3.1 V (1.49%)733.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.51 V (0.72%)206.5 V2.48 V (1.19%)586.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.54%)206.9 V1.86 V (0.9%)439.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 225 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.34V (2.57%) and delivers 202.7V at the load.

What size aluminum wire is required for 225 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.21V (2.98%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.