🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.65%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.57V (2.74%)
Voltage at Load End233.6 VLoss: 6.37 V (1433.4 W)
Power & Breaker (125%)54.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A388.07 V (161.7%)0.0 V640.13 V (266.72%)87315.9 WDrop/Amp High
12 AWG3.31 mm²20 A243.86 V (101.61%)0.0 V402.26 V (167.61%)54869.2 WDrop/Amp High
10 AWG5.26 mm²30 A153.46 V (63.94%)86.5 V253.13 V (105.47%)34527.9 WDrop/Amp High
8 AWG8.37 mm²50 A96.44 V (40.18%)143.6 V159.08 V (66.28%)21698.6 WDrop/Amp High
6 AWG13.3 mm²65 A60.69 V (25.29%)179.3 V100.11 V (41.71%)13655.4 WDrop/Amp High
4 AWG21.15 mm²85 A38.16 V (15.9%)201.8 V62.95 V (26.23%)8587.1 WDrop/Amp High
3 AWG26.67 mm²100 A30.27 V (12.61%)209.7 V49.92 V (20.8%)6809.8 WDrop/Amp High
2 AWG33.62 mm²115 A24.01 V (10.0%)216.0 V39.6 V (16.5%)5402.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.03 V (7.93%)221.0 V31.4 V (13.08%)4282.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.09 V (6.29%)224.9 V24.89 V (10.37%)3395.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.97 V (4.99%)228.0 V19.75 V (8.23%)2693.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.5 V (3.96%)230.5 V15.66 V (6.53%)2136.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.53 V (3.14%)232.5 V12.42 V (5.18%)1694.2 W~ ≤5%
250 kcmil126.7 mm²255 A6.37 V (2.65%)233.6 V10.51 V (4.38%)1433.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.31 V (2.21%)234.7 V8.76 V (3.65%)1194.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.55 V (1.9%)235.4 V7.51 V (3.13%)1024.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.98 V (1.66%)236.0 V6.57 V (2.74%)896.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.19 V (1.33%)236.8 V5.25 V (2.19%)716.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.66 V (1.11%)237.3 V4.38 V (1.82%)597.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.12 V (0.89%)237.9 V3.5 V (1.46%)477.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.59 V (0.66%)238.4 V2.63 V (1.09%)358.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 275 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.37V (2.65%) and delivers 233.6V at the load.

What size aluminum wire is required for 225 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.57V (2.74%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.