⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.42V (2.68%)
Voltage at Load End233.5 VLoss: 6.49 V (1784.9 W)
Power & Breaker (125%)66.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A474.31 V (197.63%)0.0 V782.39 V (325.99%)130434.8 WDrop/Amp High
12 AWG3.31 mm²20 A298.05 V (124.19%)0.0 V491.65 V (204.85%)81965.1 WDrop/Amp High
10 AWG5.26 mm²30 A187.56 V (78.15%)52.4 V309.39 V (128.91%)51578.8 WDrop/Amp High
8 AWG8.37 mm²50 A117.87 V (49.11%)122.1 V194.43 V (81.01%)32413.9 WDrop/Amp High
6 AWG13.3 mm²65 A74.18 V (30.91%)165.8 V122.36 V (50.98%)20398.8 WDrop/Amp High
4 AWG21.15 mm²85 A46.65 V (19.44%)193.4 V76.94 V (32.06%)12827.6 WDrop/Amp High
3 AWG26.67 mm²100 A36.99 V (15.41%)203.0 V61.02 V (25.42%)10172.6 WDrop/Amp High
2 AWG33.62 mm²115 A29.34 V (12.23%)210.7 V48.4 V (20.17%)8069.7 WDrop/Amp High
1 AWG42.41 mm²130 A23.26 V (9.69%)216.7 V38.37 V (15.99%)6397.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.44 V (7.68%)221.6 V30.42 V (12.68%)5072.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.63 V (6.1%)225.4 V24.13 V (10.06%)4023.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.61 V (4.84%)228.4 V19.14 V (7.98%)3191.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.2 V (3.83%)230.8 V15.18 V (6.33%)2530.8 WDrop/Amp High
250 kcmil126.7 mm²255 A7.79 V (3.24%)232.2 V12.84 V (5.35%)2141.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.49 V (2.7%)233.5 V10.71 V (4.46%)1784.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.56 V (2.32%)234.4 V9.18 V (3.82%)1530.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.87 V (2.03%)235.1 V8.03 V (3.35%)1338.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.89 V (1.62%)236.1 V6.42 V (2.68%)1070.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.25 V (1.35%)236.8 V5.35 V (2.23%)892.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.6 V (1.08%)237.4 V4.28 V (1.78%)714.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.95 V (0.81%)238.1 V3.21 V (1.34%)535.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 275 feet one-way at 240V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.49V (2.7%) and delivers 233.5V at the load.

What size aluminum wire is required for 275 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.42V (2.68%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.