⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.34%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 5.56V (2.32%)
Voltage at Load End234.4 VLoss: 5.62 V (2677.3 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A410.76 V (171.15%)0.0 V677.57 V (282.32%)195652.2 WDrop/Amp High
12 AWG3.31 mm²20 A258.12 V (107.55%)0.0 V425.78 V (177.41%)122947.6 WDrop/Amp High
10 AWG5.26 mm²30 A162.43 V (67.68%)77.6 V267.94 V (111.64%)77368.2 WDrop/Amp High
8 AWG8.37 mm²50 A102.08 V (42.53%)137.9 V168.38 V (70.16%)48620.9 WDrop/Amp High
6 AWG13.3 mm²65 A64.24 V (26.77%)175.8 V105.97 V (44.15%)30598.2 WDrop/Amp High
4 AWG21.15 mm²85 A40.4 V (16.83%)199.6 V66.64 V (27.76%)19241.4 WDrop/Amp High
3 AWG26.67 mm²100 A32.04 V (13.35%)208.0 V52.84 V (22.02%)15259.0 WDrop/Amp High
2 AWG33.62 mm²115 A25.41 V (10.59%)214.6 V41.92 V (17.47%)12104.6 WDrop/Amp High
1 AWG42.41 mm²130 A20.15 V (8.39%)219.9 V33.23 V (13.85%)9595.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.97 V (6.66%)224.0 V26.35 V (10.98%)7608.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.67 V (5.28%)227.3 V20.9 V (8.71%)6035.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.05 V (4.19%)229.9 V16.58 V (6.91%)4787.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.97 V (3.32%)232.0 V13.15 V (5.48%)3796.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.74 V (2.81%)233.3 V11.12 V (4.63%)3212.0 WDrop/Amp High
300 kcmil152.0 mm²285 A5.62 V (2.34%)234.4 V9.27 V (3.86%)2677.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.82 V (2.01%)235.2 V7.95 V (3.31%)2295.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.22 V (1.76%)235.8 V6.95 V (2.9%)2007.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.37 V (1.4%)236.6 V5.56 V (2.32%)1606.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.81 V (1.17%)237.2 V4.64 V (1.93%)1338.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.25 V (0.94%)237.8 V3.71 V (1.55%)1070.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.69 V (0.7%)238.3 V2.78 V (1.16%)803.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 275 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 5.62V (2.34%) and delivers 234.4V at the load.

What size aluminum wire is required for 275 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 5.56V (2.32%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.