🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.58V (2.68%)
Voltage at Load End202.9 VLoss: 5.07 V (2854.8 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A617.84 V (297.04%)0.0 V1019.15 V (489.98%)347793.5 WDrop/Amp High
12 AWG3.31 mm²20 A388.25 V (186.66%)0.0 V640.43 V (307.9%)218553.0 WDrop/Amp High
10 AWG5.26 mm²30 A244.32 V (117.46%)0.0 V403.01 V (193.75%)137530.5 WDrop/Amp High
8 AWG8.37 mm²50 A153.54 V (73.82%)54.5 V253.27 V (121.76%)86429.0 WDrop/Amp High
6 AWG13.3 mm²65 A96.62 V (46.45%)111.4 V159.39 V (76.63%)54391.8 WDrop/Amp High
4 AWG21.15 mm²85 A60.76 V (29.21%)147.2 V100.23 V (48.19%)34203.8 WDrop/Amp High
3 AWG26.67 mm²100 A48.19 V (23.17%)159.8 V79.48 V (38.21%)27124.5 WDrop/Amp High
2 AWG33.62 mm²115 A38.22 V (18.38%)169.8 V63.05 V (30.31%)21517.3 WDrop/Amp High
1 AWG42.41 mm²130 A30.3 V (14.57%)177.7 V49.98 V (24.03%)17057.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.03 V (11.55%)184.0 V39.63 V (19.05%)13524.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.06 V (9.16%)188.9 V31.44 V (15.11%)10728.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.12 V (7.27%)192.9 V24.94 V (11.99%)8509.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.99 V (5.76%)196.0 V19.77 V (9.51%)6748.2 WDrop/Amp High
250 kcmil126.7 mm²255 A10.14 V (4.88%)197.9 V16.73 V (8.04%)5709.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.45 V (4.06%)199.5 V13.95 V (6.7%)4759.3 WDrop/Amp High
350 kcmil177.3 mm²310 A7.25 V (3.48%)200.8 V11.96 V (5.75%)4080.1 WDrop/Amp High
400 kcmil202.7 mm²335 A6.34 V (3.05%)201.7 V10.46 V (5.03%)3568.9 W~ ≤5%
500 kcmil253.4 mm²380 A5.07 V (2.44%)202.9 V8.37 V (4.02%)2854.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.23 V (2.03%)203.8 V6.97 V (3.35%)2379.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.38 V (1.63%)204.6 V5.58 V (2.68%)1903.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.54 V (1.22%)205.5 V4.18 V (2.01%)1427.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 350 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.07V (2.44%) and delivers 202.9V at the load.

What size aluminum wire is required for 325 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.58V (2.68%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.