⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.64%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.97V (2.91%)
Voltage at Load End233.7 VLoss: 6.34 V (3568.9 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A617.84 V (257.43%)0.0 V1019.15 V (424.65%)347793.5 WDrop/Amp High
12 AWG3.31 mm²20 A388.25 V (161.77%)0.0 V640.43 V (266.85%)218553.0 WDrop/Amp High
10 AWG5.26 mm²30 A244.32 V (101.8%)0.0 V403.01 V (167.92%)137530.5 WDrop/Amp High
8 AWG8.37 mm²50 A153.54 V (63.97%)86.5 V253.27 V (105.53%)86429.0 WDrop/Amp High
6 AWG13.3 mm²65 A96.62 V (40.26%)143.4 V159.39 V (66.41%)54391.8 WDrop/Amp High
4 AWG21.15 mm²85 A60.76 V (25.32%)179.2 V100.23 V (41.76%)34203.8 WDrop/Amp High
3 AWG26.67 mm²100 A48.19 V (20.08%)191.8 V79.48 V (33.12%)27124.5 WDrop/Amp High
2 AWG33.62 mm²115 A38.22 V (15.93%)201.8 V63.05 V (26.27%)21517.3 WDrop/Amp High
1 AWG42.41 mm²130 A30.3 V (12.63%)209.7 V49.98 V (20.83%)17057.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.03 V (10.01%)216.0 V39.63 V (16.51%)13524.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.06 V (7.94%)220.9 V31.44 V (13.1%)10728.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.12 V (6.3%)224.9 V24.94 V (10.39%)8509.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.99 V (4.99%)228.0 V19.77 V (8.24%)6748.2 WDrop/Amp High
250 kcmil126.7 mm²255 A10.14 V (4.23%)229.9 V16.73 V (6.97%)5709.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.45 V (3.52%)231.5 V13.95 V (5.81%)4759.3 WDrop/Amp High
350 kcmil177.3 mm²310 A7.25 V (3.02%)232.8 V11.96 V (4.98%)4080.1 WDrop/Amp High
400 kcmil202.7 mm²335 A6.34 V (2.64%)233.7 V10.46 V (4.36%)3568.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.07 V (2.11%)234.9 V8.37 V (3.49%)2854.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.23 V (1.76%)235.8 V6.97 V (2.91%)2379.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.38 V (1.41%)236.6 V5.58 V (2.32%)1903.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.54 V (1.06%)237.5 V4.18 V (1.74%)1427.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 350 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 6.34V (2.64%) and delivers 233.7V at the load.

What size aluminum wire is required for 325 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.97V (2.91%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.