🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 400 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (4.6%)
Voltage at Load End116.7 VLoss: 3.35 V (1087.8 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 400 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A815.34 V (679.45%)0.0 V1344.93 V (1120.78%)264985.5 WDrop/Amp High
12 AWG3.31 mm²20 A512.36 V (426.97%)0.0 V845.15 V (704.29%)166516.6 WDrop/Amp High
10 AWG5.26 mm²30 A322.42 V (268.68%)0.0 V531.84 V (443.2%)104785.1 WDrop/Amp High
8 AWG8.37 mm²50 A202.62 V (168.85%)0.0 V334.22 V (278.52%)65850.6 WDrop/Amp High
6 AWG13.3 mm²65 A127.51 V (106.26%)0.0 V210.33 V (175.28%)41441.3 WDrop/Amp High
4 AWG21.15 mm²85 A80.18 V (66.82%)39.8 V132.27 V (110.22%)26060.0 WDrop/Amp High
3 AWG26.67 mm²100 A63.59 V (52.99%)56.4 V104.89 V (87.41%)20666.3 WDrop/Amp High
2 AWG33.62 mm²115 A50.44 V (42.04%)69.6 V83.21 V (69.34%)16394.1 WDrop/Amp High
1 AWG42.41 mm²130 A39.99 V (33.32%)80.0 V65.96 V (54.97%)12996.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.71 V (26.42%)88.3 V52.3 V (43.58%)10304.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.15 V (20.96%)94.8 V41.49 V (34.57%)8174.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.95 V (16.62%)100.1 V32.91 V (27.42%)6483.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.82 V (13.18%)104.2 V26.1 V (21.75%)5141.5 WDrop/Amp High
250 kcmil126.7 mm²255 A13.39 V (11.15%)106.6 V22.08 V (18.4%)4350.2 WDrop/Amp High
300 kcmil152.0 mm²285 A11.16 V (9.3%)108.8 V18.4 V (15.34%)3626.1 WDrop/Amp High
350 kcmil177.3 mm²310 A9.57 V (7.97%)110.4 V15.78 V (13.15%)3108.7 WDrop/Amp High
400 kcmil202.7 mm²335 A8.37 V (6.97%)111.6 V13.8 V (11.5%)2719.1 WDrop/Amp High
500 kcmil253.4 mm²380 A6.69 V (5.58%)113.3 V11.04 V (9.2%)2175.1 WDrop/Amp High
600 kcmil304.0 mm²420 A5.58 V (4.65%)114.4 V9.2 V (7.67%)1813.1 W~ ≤5%
750 kcmil380.0 mm²475 A4.46 V (3.72%)115.5 V7.36 V (6.13%)1450.4 W~ ≤5%
1000 kcmil506.7 mm²545 A3.35 V (2.79%)116.7 V5.52 V (4.6%)1087.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 400 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 400 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.35V (2.79%) and delivers 116.7V at the load.

What size aluminum wire is required for 325 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (4.6%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.