🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.35V (4.31%)
Voltage at Load End233.7 VLoss: 6.28 V (2039.6 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1528.76 V (636.98%)0.0 V2521.74 V (1050.73%)496847.8 WDrop/Amp High
12 AWG3.31 mm²20 A960.67 V (400.28%)0.0 V1584.66 V (660.28%)312218.6 WDrop/Amp High
10 AWG5.26 mm²30 A604.53 V (251.89%)0.0 V997.19 V (415.5%)196472.1 WDrop/Amp High
8 AWG8.37 mm²50 A379.91 V (158.29%)0.0 V626.67 V (261.11%)123469.9 WDrop/Amp High
6 AWG13.3 mm²65 A239.08 V (99.62%)0.9 V394.38 V (164.32%)77702.5 WDrop/Amp High
4 AWG21.15 mm²85 A150.35 V (62.64%)89.7 V248.0 V (103.33%)48862.6 WDrop/Amp High
3 AWG26.67 mm²100 A119.23 V (49.68%)120.8 V196.67 V (81.95%)38749.3 WDrop/Amp High
2 AWG33.62 mm²115 A94.58 V (39.41%)145.4 V156.02 V (65.01%)30738.9 WDrop/Amp High
1 AWG42.41 mm²130 A74.98 V (31.24%)165.0 V123.68 V (51.53%)24367.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A59.45 V (24.77%)180.6 V98.06 V (40.86%)19320.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.16 V (19.65%)192.8 V77.79 V (32.41%)15326.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.41 V (15.59%)202.6 V61.7 V (25.71%)12156.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A29.66 V (12.36%)210.3 V48.93 V (20.39%)9640.3 WDrop/Amp High
250 kcmil126.7 mm²255 A25.1 V (10.46%)214.9 V41.4 V (17.25%)8156.6 WDrop/Amp High
300 kcmil152.0 mm²285 A20.92 V (8.72%)219.1 V34.51 V (14.38%)6799.0 WDrop/Amp High
350 kcmil177.3 mm²310 A17.93 V (7.47%)222.1 V29.58 V (12.33%)5828.8 WDrop/Amp High
400 kcmil202.7 mm²335 A15.69 V (6.54%)224.3 V25.88 V (10.78%)5098.4 WDrop/Amp High
500 kcmil253.4 mm²380 A12.55 V (5.23%)227.5 V20.7 V (8.62%)4078.3 WDrop/Amp High
600 kcmil304.0 mm²420 A10.46 V (4.36%)229.5 V17.25 V (7.19%)3399.5 W~ ≤5%
750 kcmil380.0 mm²475 A8.37 V (3.49%)231.6 V13.8 V (5.75%)2719.6 W~ ≤5%
1000 kcmil506.7 mm²545 A6.28 V (2.61%)233.7 V10.35 V (4.31%)2039.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 750 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.28V (2.61%) and delivers 233.7V at the load.

What size aluminum wire is required for 325 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.35V (4.31%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.