🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 12.75V (2.66%)
Voltage at Load End468.4 VLoss: 11.59 V (6525.3 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1412.21 V (294.21%)0.0 V2329.49 V (485.31%)794956.5 WDrop/Amp High
12 AWG3.31 mm²20 A887.43 V (184.88%)0.0 V1463.85 V (304.97%)499549.7 WDrop/Amp High
10 AWG5.26 mm²30 A558.44 V (116.34%)0.0 V921.17 V (191.91%)314355.4 WDrop/Amp High
8 AWG8.37 mm²50 A350.94 V (73.11%)129.1 V578.89 V (120.6%)197551.9 WDrop/Amp High
6 AWG13.3 mm²65 A220.86 V (46.01%)259.1 V364.31 V (75.9%)124324.0 WDrop/Amp High
4 AWG21.15 mm²85 A138.88 V (28.93%)341.1 V229.09 V (47.73%)78180.1 WDrop/Amp High
3 AWG26.67 mm²100 A110.14 V (22.95%)369.9 V181.68 V (37.85%)61998.9 WDrop/Amp High
2 AWG33.62 mm²115 A87.37 V (18.2%)392.6 V144.12 V (30.03%)49182.3 WDrop/Amp High
1 AWG42.41 mm²130 A69.26 V (14.43%)410.7 V114.25 V (23.8%)38988.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.91 V (11.44%)425.1 V90.58 V (18.87%)30912.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.56 V (9.08%)436.4 V71.86 V (14.97%)24521.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.55 V (7.2%)445.4 V57.0 V (11.87%)19450.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.4 V (5.71%)452.6 V45.2 V (9.42%)15424.5 WDrop/Amp High
250 kcmil126.7 mm²255 A23.18 V (4.83%)456.8 V38.24 V (7.97%)13050.6 WDrop/Amp High
300 kcmil152.0 mm²285 A19.32 V (4.03%)460.7 V31.88 V (6.64%)10878.4 WDrop/Amp High
350 kcmil177.3 mm²310 A16.57 V (3.45%)463.4 V27.33 V (5.69%)9326.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.49 V (3.02%)465.5 V23.9 V (4.98%)8157.4 W~ ≤5%
500 kcmil253.4 mm²380 A11.59 V (2.41%)468.4 V19.12 V (3.98%)6525.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A9.66 V (2.01%)470.3 V15.94 V (3.32%)5439.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A7.73 V (1.61%)472.3 V12.75 V (2.66%)4351.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.8 V (1.21%)474.2 V9.56 V (1.99%)3263.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 800 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 11.59V (2.41%) and delivers 468.4V at the load.

What size aluminum wire is required for 325 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 12.75V (2.66%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.