⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 200 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.3V (2.48%)
Voltage at Load End11.7 VLoss: 0.3 V (10.5 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 200 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A43.9 V (365.86%)0.0 V72.42 V (603.49%)1536.6 WDrop/Amp High
12 AWG3.31 mm²20 A27.59 V (229.9%)0.0 V45.51 V (379.24%)965.6 WDrop/Amp High
10 AWG5.26 mm²30 A17.36 V (144.67%)0.0 V28.64 V (238.64%)607.6 WDrop/Amp High
8 AWG8.37 mm²50 A10.91 V (90.92%)1.1 V18.0 V (149.97%)381.9 WDrop/Amp High
6 AWG13.3 mm²65 A6.87 V (57.22%)5.1 V11.33 V (94.38%)240.3 WDrop/Amp High
4 AWG21.15 mm²85 A4.32 V (35.98%)7.7 V7.12 V (59.35%)151.1 WDrop/Amp High
3 AWG26.67 mm²100 A3.42 V (28.53%)8.6 V5.65 V (47.07%)119.8 WDrop/Amp High
2 AWG33.62 mm²115 A2.72 V (22.63%)9.3 V4.48 V (37.34%)95.1 WDrop/Amp High
1 AWG42.41 mm²130 A2.15 V (17.94%)9.8 V3.55 V (29.6%)75.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.71 V (14.23%)10.3 V2.82 V (23.47%)59.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.35 V (11.29%)10.6 V2.23 V (18.62%)47.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.07 V (8.95%)10.9 V1.77 V (14.77%)37.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.85 V (7.1%)11.1 V1.41 V (11.71%)29.8 WDrop/Amp High
250 kcmil126.7 mm²255 A0.72 V (6.01%)11.3 V1.19 V (9.91%)25.2 WDrop/Amp High
300 kcmil152.0 mm²285 A0.6 V (5.01%)11.4 V0.99 V (8.26%)21.0 WDrop/Amp High
350 kcmil177.3 mm²310 A0.52 V (4.29%)11.5 V0.85 V (7.08%)18.0 W~ ≤5%
400 kcmil202.7 mm²335 A0.45 V (3.75%)11.5 V0.74 V (6.19%)15.8 W~ ≤5%
500 kcmil253.4 mm²380 A0.36 V (3.0%)11.6 V0.59 V (4.95%)12.6 W~ ≤5%
600 kcmil304.0 mm²420 A0.3 V (2.5%)11.7 V0.5 V (4.13%)10.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.24 V (2.0%)11.8 V0.4 V (3.3%)8.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (1.5%)11.8 V0.3 V (2.48%)6.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 200 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 200 feet one-way at 12V (DC), you need 600 kcmil copper wire. This produces a voltage drop of 0.3V (2.5%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.3V (2.48%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.