🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.07V (2.56%)
Voltage at Load End117.0 VLoss: 2.96 V (103.6 W)
Power & Breaker (125%)4.2 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A60.37 V (50.31%)59.6 V99.58 V (82.98%)2112.8 WDrop/Amp High
12 AWG3.31 mm²20 A37.93 V (31.61%)82.1 V62.57 V (52.14%)1327.7 WDrop/Amp High
10 AWG5.26 mm²30 A23.87 V (19.89%)96.1 V39.38 V (32.81%)835.5 WDrop/Amp High
8 AWG8.37 mm²50 A15.0 V (12.5%)105.0 V24.75 V (20.62%)525.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.44 V (7.87%)110.6 V15.57 V (12.98%)330.4 WDrop/Amp High
4 AWG21.15 mm²85 A5.94 V (4.95%)114.1 V9.79 V (8.16%)207.8 W~ ≤5%
3 AWG26.67 mm²100 A4.71 V (3.92%)115.3 V7.77 V (6.47%)164.8 W~ ≤5%
2 AWG33.62 mm²115 A3.73 V (3.11%)116.3 V6.16 V (5.13%)130.7 W~ ≤5%
1 AWG42.41 mm²130 A2.96 V (2.47%)117.0 V4.88 V (4.07%)103.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.35 V (1.96%)117.7 V3.87 V (3.23%)82.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.86 V (1.55%)118.1 V3.07 V (2.56%)65.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.48 V (1.23%)118.5 V2.44 V (2.03%)51.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.17 V (0.98%)118.8 V1.93 V (1.61%)41.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.99 V (0.83%)119.0 V1.63 V (1.36%)34.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.83 V (0.69%)119.2 V1.36 V (1.14%)28.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.71 V (0.59%)119.3 V1.17 V (0.97%)24.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.62 V (0.52%)119.4 V1.02 V (0.85%)21.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.5 V (0.41%)119.5 V0.82 V (0.68%)17.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.41 V (0.34%)119.6 V0.68 V (0.57%)14.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.28%)119.7 V0.55 V (0.45%)11.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.21%)119.8 V0.41 V (0.34%)8.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 275 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 2.96V (2.47%) and delivers 117.0V at the load.

What size aluminum wire is required for 35 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.07V (2.56%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.