🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.79%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.72V (1.97%)
Voltage at Load End235.7 VLoss: 4.29 V (2601.4 W)
Power & Breaker (125%)145.49 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A522.79 V (217.83%)0.0 V862.36 V (359.32%)316924.2 WDrop/Amp High
12 AWG3.31 mm²20 A328.52 V (136.88%)0.0 V541.9 V (225.79%)199154.8 WDrop/Amp High
10 AWG5.26 mm²30 A206.73 V (86.14%)33.3 V341.01 V (142.09%)125323.6 WDrop/Amp High
8 AWG8.37 mm²50 A129.92 V (54.13%)110.1 V214.3 V (89.29%)78757.8 WDrop/Amp High
6 AWG13.3 mm²65 A81.76 V (34.07%)158.2 V134.87 V (56.19%)49564.1 WDrop/Amp High
4 AWG21.15 mm²85 A51.41 V (21.42%)188.6 V84.81 V (35.34%)31168.0 WDrop/Amp High
3 AWG26.67 mm²100 A40.77 V (16.99%)199.2 V67.26 V (28.02%)24717.0 WDrop/Amp High
2 AWG33.62 mm²115 A32.34 V (13.48%)207.7 V53.35 V (22.23%)19607.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.64 V (10.68%)214.4 V42.29 V (17.62%)15543.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.33 V (8.47%)219.7 V33.53 V (13.97%)12323.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.13 V (6.72%)223.9 V26.6 V (11.08%)9776.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.79 V (5.33%)227.2 V21.1 V (8.79%)7754.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.14 V (4.23%)229.9 V16.73 V (6.97%)6149.3 WDrop/Amp High
250 kcmil126.7 mm²255 A8.58 V (3.58%)231.4 V14.16 V (5.9%)5202.9 WDrop/Amp High
300 kcmil152.0 mm²285 A7.15 V (2.98%)232.8 V11.8 V (4.92%)4336.9 WDrop/Amp High
350 kcmil177.3 mm²310 A6.13 V (2.56%)233.9 V10.12 V (4.22%)3718.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.36 V (2.24%)234.6 V8.85 V (3.69%)3252.1 WDrop/Amp High
500 kcmil253.4 mm²380 A4.29 V (1.79%)235.7 V7.08 V (2.95%)2601.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.58 V (1.49%)236.4 V5.9 V (2.46%)2168.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.86 V (1.19%)237.1 V4.72 V (1.97%)1734.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.15 V (0.89%)237.9 V3.54 V (1.47%)1301.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 275 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.29V (1.79%) and delivers 235.7V at the load.

What size aluminum wire is required for 350 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.72V (1.97%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.