🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.92%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.06V (2.11%)
Voltage at Load End235.4 VLoss: 4.6 V (2986.3 W)
Power & Breaker (125%)155.88 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A560.13 V (233.39%)0.0 V923.96 V (384.98%)363816.1 WDrop/Amp High
12 AWG3.31 mm²20 A351.99 V (146.66%)0.0 V580.61 V (241.92%)228621.6 WDrop/Amp High
10 AWG5.26 mm²30 A221.5 V (92.29%)18.5 V365.37 V (152.24%)143866.4 WDrop/Amp High
8 AWG8.37 mm²50 A139.2 V (58.0%)100.8 V229.61 V (95.67%)90410.7 WDrop/Amp High
6 AWG13.3 mm²65 A87.6 V (36.5%)152.4 V144.5 V (60.21%)56897.6 WDrop/Amp High
4 AWG21.15 mm²85 A55.09 V (22.95%)184.9 V90.87 V (37.86%)35779.5 WDrop/Amp High
3 AWG26.67 mm²100 A43.68 V (18.2%)196.3 V72.06 V (30.02%)28374.1 WDrop/Amp High
2 AWG33.62 mm²115 A34.65 V (14.44%)205.3 V57.16 V (23.82%)22508.5 WDrop/Amp High
1 AWG42.41 mm²130 A27.47 V (11.45%)212.5 V45.32 V (18.88%)17843.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.78 V (9.08%)218.2 V35.93 V (14.97%)14147.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.28 V (7.2%)222.7 V28.5 V (11.88%)11222.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.71 V (5.71%)226.3 V22.61 V (9.42%)8901.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.87 V (4.53%)229.1 V17.93 V (7.47%)7059.1 WDrop/Amp High
250 kcmil126.7 mm²255 A9.2 V (3.83%)230.8 V15.17 V (6.32%)5972.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.66 V (3.19%)232.3 V12.64 V (5.27%)4978.5 WDrop/Amp High
350 kcmil177.3 mm²310 A6.57 V (2.74%)233.4 V10.84 V (4.52%)4268.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.75 V (2.39%)234.3 V9.48 V (3.95%)3733.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.6 V (1.92%)235.4 V7.58 V (3.16%)2986.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.83 V (1.6%)236.2 V6.32 V (2.63%)2489.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.07 V (1.28%)236.9 V5.06 V (2.11%)1991.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.3 V (0.96%)237.7 V3.79 V (1.58%)1493.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 275 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.6V (1.92%) and delivers 235.4V at the load.

What size aluminum wire is required for 375 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.06V (2.11%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.