🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 18.05V (7.52%)
Voltage at Load End234.5 VLoss: 5.47 V (2325.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2665.53 V (1110.64%)0.0 V4396.89 V (1832.04%)1132852.2 WDrop/Amp High
12 AWG3.31 mm²20 A1675.02 V (697.92%)0.0 V2763.0 V (1151.25%)711883.0 WDrop/Amp High
10 AWG5.26 mm²30 A1054.05 V (439.19%)0.0 V1738.69 V (724.46%)447972.0 WDrop/Amp High
8 AWG8.37 mm²50 A662.4 V (276.0%)0.0 V1092.66 V (455.27%)281521.2 WDrop/Amp High
6 AWG13.3 mm²65 A416.87 V (173.69%)0.0 V687.63 V (286.51%)177167.9 WDrop/Amp High
4 AWG21.15 mm²85 A262.14 V (109.23%)0.0 V432.41 V (180.17%)111410.5 WDrop/Amp High
3 AWG26.67 mm²100 A207.89 V (86.62%)32.1 V342.91 V (142.88%)88351.4 WDrop/Amp High
2 AWG33.62 mm²115 A164.91 V (68.71%)75.1 V272.03 V (113.34%)70087.2 WDrop/Amp High
1 AWG42.41 mm²130 A130.73 V (54.47%)109.3 V215.65 V (89.85%)55560.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A103.65 V (43.19%)136.3 V170.98 V (71.24%)44051.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A82.22 V (34.26%)157.8 V135.63 V (56.51%)34944.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A65.22 V (27.17%)174.8 V107.58 V (44.83%)27718.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.72 V (21.55%)188.3 V85.31 V (35.55%)21980.7 WDrop/Amp High
250 kcmil126.7 mm²255 A43.76 V (18.23%)196.2 V72.18 V (30.08%)18597.7 WDrop/Amp High
300 kcmil152.0 mm²285 A36.48 V (15.2%)203.5 V60.17 V (25.07%)15502.2 WDrop/Amp High
350 kcmil177.3 mm²310 A31.27 V (13.03%)208.7 V51.58 V (21.49%)13290.1 WDrop/Amp High
400 kcmil202.7 mm²335 A27.35 V (11.4%)212.6 V45.12 V (18.8%)11624.7 WDrop/Amp High
500 kcmil253.4 mm²380 A21.88 V (9.12%)218.1 V36.09 V (15.04%)9298.9 WDrop/Amp High
600 kcmil304.0 mm²420 A18.24 V (7.6%)221.8 V30.08 V (12.53%)7751.1 WDrop/Amp High
750 kcmil380.0 mm²475 A14.59 V (6.08%)225.4 V24.07 V (10.03%)6200.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4650.4 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.47V (2.28%) and delivers 234.5V at the load.

What size aluminum wire is required for 425 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 18.05V (7.52%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.