🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.76%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.95V (0.94%)
Voltage at Load End206.4 VLoss: 1.58 V (1162.7 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A288.55 V (138.73%)0.0 V475.98 V (228.84%)212409.8 WDrop/Amp High
12 AWG3.31 mm²20 A181.33 V (87.18%)26.7 V299.1 V (143.8%)133478.1 WDrop/Amp High
10 AWG5.26 mm²30 A114.1 V (54.86%)93.9 V188.22 V (90.49%)83994.7 WDrop/Amp High
8 AWG8.37 mm²50 A71.71 V (34.47%)136.3 V118.28 V (56.87%)52785.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.13 V (21.7%)162.9 V74.44 V (35.79%)33219.0 WDrop/Amp High
4 AWG21.15 mm²85 A28.38 V (13.64%)179.6 V46.81 V (22.5%)20889.5 WDrop/Amp High
3 AWG26.67 mm²100 A22.5 V (10.82%)185.5 V37.12 V (17.85%)16565.9 WDrop/Amp High
2 AWG33.62 mm²115 A17.85 V (8.58%)190.1 V29.45 V (14.16%)13141.4 WDrop/Amp High
1 AWG42.41 mm²130 A14.15 V (6.8%)193.8 V23.34 V (11.22%)10417.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.22 V (5.39%)196.8 V18.51 V (8.9%)8259.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.9 V (4.28%)199.1 V14.68 V (7.06%)6552.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.06 V (3.39%)200.9 V11.65 V (5.6%)5197.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.6 V (2.69%)202.4 V9.24 V (4.44%)4121.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.74 V (2.28%)203.3 V7.81 V (3.76%)3487.1 WDrop/Amp High
300 kcmil152.0 mm²285 A3.95 V (1.9%)204.1 V6.51 V (3.13%)2906.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.39 V (1.63%)204.6 V5.58 V (2.68%)2491.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.96 V (1.42%)205.0 V4.88 V (2.35%)2179.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.37 V (1.14%)205.6 V3.91 V (1.88%)1743.5 WDrop/Amp High
600 kcmil304.0 mm²420 A1.97 V (0.95%)206.0 V3.26 V (1.57%)1453.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.58 V (0.76%)206.4 V2.61 V (1.25%)1162.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.18 V (0.57%)206.8 V1.95 V (0.94%)871.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 125 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.58V (0.76%) and delivers 206.4V at the load.

What size aluminum wire is required for 425 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.95V (0.94%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.